Permit Information
Permit NumberBLD11-01089
StatusFinaled
Name CAPITOL TERRACE CONDO ASSOC
Site Address 110 N 8TH ST
Project NameCAPITAL TERRACE
Customer Number 
ePlanReviewNo
Description
(FETE STYLE BAR) Remodel an existing 1,832 sq. ft. space changing use from retail to new hair salon tenant on first floor of existing building. Work to include: Upgrades to the ramped area at the entry of this space per plans; upgrades to the existing restroom per plans; install a new dual height (hi-lo) accessible drinking fountain; installation of a new plumbing chase per plans; installation of new lavatories and work surface counters; interior finishes in compliance with chapter 8 of the 2009 IBC; and plumbing work. All work per the approved plans, attached plan review report, and all other reviewing agencies approvals. NOTE: This building is fully fire sprinklered for high-rise provisions. Any alterations or modifications to the fire sprinkler system shall be per NFPA #13 as regulated by the fire department and will require a separate permit. No new lighting or mechanical work is proposed or allowed under this permit. A new Certificate of Occupancy with the new occupant load total is required to be obtained after all work has been inspected and approved and prior to tenant occupying this space. **SRZ**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/4/20118/8/20118/8/2011APASS
DetailsDave Hannah
ben Phone #: ###-#### ok for perm occ per Jim storey after fire finalss
FIRE-Final Inspection7/7/20118/5/20118/5/2011APASS
DetailsTroy Cobbley
Life safety passed
FIRE-Final Inspection8/3/20118/4/20118/4/2011PPASS
DetailsTroy Cobbley
life safety passed
BLD-Final7/5/20117/7/20117/7/2011PNR
DetailsJim Storey
ken Phone #: ###-####
FIRE-Final Inspection7/5/20117/7/20117/7/2011APART
DetailsTroy Cobbley
A 30 day temporary occupancy for life safety was given with Gordan's permission until the fire alarm is addressed.
FIRE-Conference7/6/20117/6/20117/6/2011ADONE
DetailsTroy Cobbley
Amy did not arrive but another lady did and I let her know that Gordan with the Boise Fire Dept was ok with a 30 day temporary occupancy as long as the door hardware and the fire sprinklers were addressed. This would leave the fire alarm modifications needing to be completed.
FIRE-Final Inspection7/5/20117/5/20117/6/2011PFAIL
DetailsTroy Cobbley
No items on the correction notice have been addressed.
BLD-Final7/5/20117/5/20117/5/2011PNR
DetailsTom Arcoraci
Ben Phone #: ###-####
FIRE-Final Inspection7/1/20117/1/20117/1/2011PFAIL
DetailsTroy Cobbley
Provide single action hardware on the restroom and breakroom doors. Replace all painted sprinkler heads as discussed and per NFPA 13 6.2.6.2. Provide for fire alarm notification in the restroom, washroom and breakroom. This work will require permit. Situation was discussed with Ben.
BLD-Final6/30/20116/30/20116/30/2011PNR
DetailsDave Hannah
Ben-Please call prior to inspection Phone #: ###-#### needs other trades finaled first