BLD-Final | 6/27/2012 | 6/28/2012 | 6/28/2012 | P | PASS |
Jim Sly
|
|
|
please call 20min prior for access - -Don Phone #: ###-#### OK for Perm Occ.
|
BLD-Final | 6/26/2012 | 6/27/2012 | 6/27/2012 | A | PART |
Mike Jordan
|
|
|
Don-PLease call at least 15 mins prior to inspection Phone #: ###-####. ok for temp occ. Needs blower door test and energy cert.
|
FIRE-Final Inspection | 6/25/2012 | 6/26/2012 | 6/26/2012 | A | PASS |
Forrest France
|
|
|
Fire life safety inspection passed.
|
FIRE-Final Inspection | 6/22/2012 | 6/25/2012 | 6/25/2012 | A | CANC |
Forrest France
|
|
|
Overbooked
|
FIRE-Final Inspection | 6/18/2012 | 6/19/2012 | 6/19/2012 | A | FAIL |
Troy Cobbley
|
|
|
Need the project related fire alarm and fire sprinkler permits finaled. Also I found four smoke alarms on the second floor that need to be relocated to be more than the required 36" from the restroom door. The fire extinguishers need to have a current inspection tag as well.
|
BLD-Other | 4/18/2012 | 4/19/2012 | 4/19/2012 | P | PASS |
Mike Jordan
|
|
|
don Phone #: ###-####. !hr. walls and penetrations ok.
|
BLD-Other | 4/12/2012 | 4/13/2012 | 4/13/2012 | A | PASS |
Mike Jordan
|
|
|
Fire wall inspection please-Don--the 3 on the south end are the ones to be inspected please Phone #: ###-####. 5/8 type X rock on party walls for the 3 most southern units. screw pattern and all firestopping completed and is ok.
|
BLD-Framing/Rough-in | 4/10/2012 | 4/11/2012 | 4/11/2012 | A | PASS |
Mike Jordan
|
|
|
for cover in garage//Don Phone #: ###-####
|
FIRE-Conference | 4/10/2012 | 4/10/2012 | 4/10/2012 | P | DONE |
Troy Cobbley
|
|
|
I went over possible pendant sprinkler obstructions due to light fixtures with the project superintendant. Also went over fire extinguisher placement and fire dept. access.
|
BLD-Other | 4/4/2012 | 4/5/2012 | 4/5/2012 | A | PASS |
Mike Jordan
|
|
|
fire wall insp//Don Phone #: ###-####
|
BLD-Other | 4/3/2012 | 4/3/2012 | 4/3/2012 | P | PART |
Mike Jordan
|
|
|
Draftstop at party walls from ceiling to underside of roof deck and 5/8" type x rock at same location. work in progress.
|
BLD-Energy code compliance | 4/2/2012 | 4/3/2012 | 4/3/2012 | A | PASS |
Mike Jordan
|
|
|
Don Phone #: ###-####
|
BLD-Framing/Rough-in | 3/28/2012 | 3/30/2012 | 3/30/2012 | A | PART |
Mike Jordan
|
|
|
Don Phone #: ###-####. Ok to insulate. Needs to complete draft stops.
|
BLD-Framing/Rough-in | 3/27/2012 | 3/28/2012 | 3/28/2012 | P | PART |
Mike Jordan
|
|
|
don Phone #: ###-####
|
BLD-Framing/Rough-in | 3/23/2012 | 3/26/2012 | 3/26/2012 | A | PART |
Mike Jordan
|
|
|
Don Phone #: ###-####. Complete fireblocking and putty pads on party walls.
|
BLD-Conference | 12/28/2011 | 12/29/2011 | 12/29/2011 | A | PASS |
Jim Storey
|
|
|
rick Phone #: ###-#### ok to cover exterior.
|
BLD-Conference | 10/28/2011 | 10/31/2011 | 10/31/2011 | A | PASS |
Mike Jordan
|
|
|
rick - 9:00 - floor Phone #: ###-####
|