BLD-Final | 12/4/2012 | 12/5/2012 | 12/5/2012 | A | PASS |
Tony Young
|
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Hunter // done
|
DOC - Permit Finaled | 12/5/2012 | 12/5/2012 | 12/5/2012 | P | PASS |
Tony Young
|
|
|
done
|
BLD-Final | 4/9/2012 | 4/9/2012 | 4/9/2012 | P | PEND |
Tony Young
|
|
|
Bob Phone #: ###-####,, need final letter from archtect/engineer as ok as built,, all else ok
|
BLD-Conference | 4/3/2012 | 4/3/2012 | 4/3/2012 | P | PART |
Tony Young
|
|
|
bob Phone #: ###-####,, ?s on final
|
BLD-Wall cover | 12/20/2011 | 12/20/2011 | 12/20/2011 | P | PASS |
Tony Young
|
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Hunter,, energy code ok
|
BLD-Energy code compliance | 12/15/2011 | 12/16/2011 | 12/19/2011 | P | PART |
Tony Young
|
|
|
work in progress,, ok to cover ceiling when ready,,, sprinkler is passed
|
BLD-Framing/Rough-in | 12/15/2011 | 12/16/2011 | 12/16/2011 | A | PART |
Tony Young
|
|
|
bob Phone #: ###-####,, ok to insulate pending sprinkler rough pass
|
BLD-Framing/Rough-in | 12/14/2011 | 12/15/2011 | 12/15/2011 | A | PART |
Tony Young
|
|
|
bob Phone #: ###-####,,, frame ok pending
|
BLD-Energy code compliance | 12/14/2011 | 12/14/2011 | 12/14/2011 | P | NR |
Tony Young
|
|
|
bob Phone #: ###-####
|
BLD-Conference | 12/1/2011 | 12/1/2011 | 12/2/2011 | P | PART |
Tony Young
|
|
|
Bob Phone #: ###-####,, flue vs. top plate ?s
|
BLD-Framing/Rough-in | 11/28/2011 | 11/28/2011 | 11/28/2011 | P | PART |
Tony Young
|
|
|
Shear inspection please-Bob Phone #: ###-####,,, exterior shear ok
|
BLD-Foundation | 11/3/2011 | 11/4/2011 | 11/4/2011 | A | FAIL |
Mike Jordan
|
|
|
bob Phone #: ###-#### Approved plans call for special inspection for masonry, concrete and steel. Cleanouts are required for grout lifts exceeding 5ft. in height, Also clean out all mortar fins. Noted that p[lans show to grout solid only cells with reinforcement, no grout stop in wall was noted, Needs to check with engineer to ensure that steel beam will hold the additional weight of the grout. Correction notice posted, also spoke to project super about corrections.
|
BLD-Foundation | 10/14/2011 | 10/17/2011 | 10/17/2011 | A | PASS |
Tony Young
|
|
|
bob Phone #: ###-####
|
BLD-Foundation | 9/1/2011 | 9/1/2011 | 9/1/2011 | P | PART |
Tony Young
|
|
|
jay Phone #: ###-####
|
BLD-Footing | 8/24/2011 | 8/25/2011 | 8/25/2011 | A | PASS |
Tony Young
|
|
|
Jay Phone #: ###-####
|
BLD-Footing | 8/24/2011 | 8/24/2011 | 8/24/2011 | P | NR |
Tony Young
|
|
|
Jay Phone #: ###-####,, on site conf only
|