Information based on query as of Thursday, July 3, 2025.
Permit Information
Permit NumberBLD11-02408
StatusFinaled
Name CICO OF IDAHO LLC
Site Address 12000 W FRANKLIN RD
Project NameRekluse
Customer Number 
ePlanReviewNo
Description
**(REKLUSE)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 14,400 square foot office / factory building. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. This building was last occupied by “Tuff Sheds” under BLD07-02008. There are no changes to occupancy or use under this permit. TLW
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection11/2/201111/3/201111/3/2011PPASS
DetailsTroy Cobbley
Life safety passed.
BLD-Final11/2/201111/3/201111/3/2011PPASS
DetailsMike Jordan
Dwayne Dayley Phone #: ###-####. OK for perm occ.
BLD-Final10/19/201110/20/201110/20/2011PCANC
DetailsJim Storey
Dwayne-PLease call at least 30 mins prior to inspection Phone #: ###-#### fire insp. call and had a list of c/n needed. no insp. performed until fire is resolved.
FIRE-Final Inspection10/19/201110/20/201110/20/2011AFAIL
DetailsTroy Cobbley
Repair the exit signs and emergency lighting on the first floor. Provide exit signs and emergency lighting for the main lobby. Provide exit signs and emergency lighting for the second floor. Provide monitoring for the fire sprinkler monitoring panel that has been disabled. Provide sprinkler modifications for the blocked and painted sprinkler heads. Provide resubmitted plans with floor layout that matches.