BLD-Conference | 6/7/2012 | 6/12/2012 | 6/12/2012 | P | PASS |
Dave Hannah
|
|
|
Instruct tenant to complete occupancy request card and obtain final CO. ok for co
|
BLD-Aging Inspection | 5/3/2012 | 5/3/2012 | 5/3/2012 | | PASS |
Dave Hannah
|
|
|
|
DOC - Permit Finaled | 5/3/2012 | 5/3/2012 | 5/3/2012 | P | PASS |
Dave Hannah
|
|
|
|
BLD-Final | 2/22/2012 | 2/22/2012 | 2/22/2012 | A | PART |
Dave Hannah
|
|
|
Phone #: 2088701943 >> Inspection requested via mobile web by Kyle ok for temp occ after mec issues are done
|
FIRE-Final Inspection | 2/21/2012 | 2/22/2012 | 2/22/2012 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
BLD-Final | 2/20/2012 | 2/21/2012 | 2/22/2012 | P | CANC |
Dave Hannah
|
|
|
Phone #: 2088701943 >> Inspection requested via mobile web by Kyle
|
FIRE-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 | P | FAIL |
Troy Cobbley
|
|
|
The emergency lighting and exit signs have been repaired except for the two exit discharge lights and the emergency lights at the main northeast exit. Rescheduled for tomorrow morning.
|
FIRE-Final Inspection | 2/21/2012 | 2/21/2012 | 2/21/2012 | A | FAIL |
Troy Cobbley
|
|
|
Provide exit discharge lighting over the two northeast exterior exit doors per plan review, repair the emergency light just inside the main exit doors, repair the emergency light on the east side of the kitchen, provide the missing exit sign in the kitchen.
|
FIRE-Sprinkler Rough-in | 2/16/2012 | 2/16/2012 | 2/16/2012 | A | PART |
Forrest France
|
|
|
Ceilings at the opposite side of the new tenant demising wall to be maintained due to existing fire sprinkler protection. New pendent at this area to be installed per approved drawings.
|
FIRE-Conference | 2/13/2012 | 2/13/2012 | 2/14/2012 | P | DONE |
Forrest France
|
|
|
Regarding location of the manual pull station for the hood suppression system. Also discussed project related fire sprinkler work and general life safety conditions.
|
BLD-Framing/Rough-in | 2/13/2012 | 2/14/2012 | 2/14/2012 | A | PASS |
Dave Hannah
|
|
|
kyle - grid inspection Phone #: ###-####
|
BLD-Conference | 2/7/2012 | 2/8/2012 | 2/9/2012 | A | PART |
Dave Hannah
|
|
|
Kyle Phone #: ###-#### needs to make second exit ada complant
|
BLD-Wall cover | 1/5/2012 | 1/6/2012 | 1/6/2012 | A | PASS |
Dave Hannah
|
|
|
Call prior to going Phone #: 2088701943 >> Inspection requested via mobile web by Kyle ok to cover walls and ceiling soffits
|