Information based on query as of Thursday, July 4, 2024.
Permit Information
Permit NumberBLD11-02578
StatusFinaled
Name HAYS CONSTRUCTION COMPANY INC
Site Address 1195 N MILWAUKEE
Project NameNATURAL GROCERS
Customer Number 
ePlanReviewNo
Description
(NATURAL GROCERS) (CZC11-00225) This building has a fire sprinkler system for building area increase and for fire area. To remodel an existing 20,120 square foot building for a new retail sales tenant (grocery store). A demonstration kitchen classroom will be provided. It will be an A-3 Occupancy. A grease hood will be installed above the range. A grease trap will be installed on the sink. Work is to include 2 restrooms accessible to the disabled, a toilet/shower room accessible to the disabled, interior nonbearing walls, gypsum board bulkheads suspended from the roof deck, gypsum board ceilings, suspended acoustical ceilings, suspended wood ceilings, walk-in freezer and refrigerators, display shelving, millwork, and interior finishes. An air curtain will be installed at the entry vestibule. A 750 square office mezzanine will also be constructed. Structural work includes concrete footings, steel columns, steel floor joists, steel bracing rods, “forto-crete” floor sheathing, and a steel stairway. In addition, the existing steel roof trusses will be altered to increase their capacity to support added equipment loads on the roof. An interior nonstructural demolition and partial permit was issued on December 7, 2011. See BLD11-02862 for the extent of work allowed under that permit. The work is required to comply with the approved drawings, with the plan review report, with the structural calculations, and with all adopted codes and ordinances. Special Inspection is required for welding and epoxy anchors. Modifications to the existing steel roof joists and girders are required to be in accordance with the manufacturer’s specifications. A separate permit is required for storage racks where storage will be more than 8 feet above the floor. The structural design for the steel stairway is a deferred submittal item. The fire alarm is required to comply with NFPA 72 and the fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/14/20122/14/20122/14/2012PPASS
DetailsMike Jordan
need final inspection pass for occupancy, electrical signed off now. ok for perm occ.
BLD-Final2/13/20122/14/20122/14/2012APART
DetailsMike Jordan
tim Phone #: ###-####. Ok for temp occ. Will be ok for perm occ. once electrical signs off perm.
FIRE-Final Inspection2/13/20122/14/20122/14/2012APASS
DetailsTroy Cobbley
Life safety passed. The security grill is being cut down and the welded leaf of the north exit door is being blocked off with a wall extention.
BLD-Framing/Rough-in2/13/20122/13/20122/13/2012PPASS
DetailsMike Jordan
tim Phone #: ###-####. Interior steel stud framed wall for door infill as per architect addendum at northwest double door were one leaf has been welded, total egress width still ok. Roll up gate is in process of being removed.
BLD-Final2/9/20122/10/20122/10/2012PFAIL
DetailsMike Jordan
TIM Phone #: ###-####. Needs to provide correct hardware on roll down gate at front of store or render gate inactive. Unweld leaf at north west double door, and provide correct hardware or provide letter to building official for alternate approval.
FIRE-Final Inspection2/9/20122/10/20122/10/2012AFAIL
DetailsTroy Cobbley
Mount the fire extinguisher on the column in the sales/kitchen area as shown on the approved plans. The double exit doors by the Nutritunist room have one leaf that is welded shut and the panic hardware has been removed. This door needs to be returned to a functional condition or have the architect contact plan review for another consideration/alternative. Provide occupant load sign "66" for the Assembly area at the Display Kitchen. The main exit door out the front of the building has a motorized roll down security door that can be utilized to block the door. This door is not shown on the floor plans but is shown on a iso view on another plan sheet. This door does not have ADA compliant hardware. This door needs to be permanantly disabled or meet all door requirements of IFC chapter 10. Contact the building plan review for direction prior to installing hardware. Provide signage for the fire sprinkler riser location as per review note #8 and per discussion.
FIRE-Final Inspection2/8/20122/9/20122/9/2012ACANC
DetailsTroy Cobbley
Cancelled due to time constraints and Micron facilities plan review
FIRE-Conference2/8/20122/8/20122/8/2012PDONE
DetailsTroy Cobbley
I went over life safety requirements and inspection scheduling with the builder and Kevin Stees of Natural Foods.
FIRE-Conference1/23/20121/23/20121/23/2012PDONE
DetailsTroy Cobbley
I went over exit sign placement with the electrician. The superintendant and I went over the need to verify the wood above the ceiling as being fire rated.
BLD-Other1/23/20121/23/20121/23/2012PPASS
DetailsMike Jordan
Hardlids ok.
BLD-Framing/Rough-in1/18/20121/18/20121/18/2012PNR
DetailsMike Jordan
tim Phone #: ###-####. Needs fire sprinkler rough in inspection.
BLD-Framing/Rough-in1/11/20121/11/20121/11/2012PPASS
DetailsMike Jordan
TIM Phone #: ###-####. Interior steel stud walls at sales floor area and restrooms. No grid or hardlids.
BLD-Other1/4/20121/4/20121/4/2012PCANC
DetailsMike Jordan
Tim-Screw inspection please Phone #: ###-####
BLD-Framing/Rough-in1/4/20121/4/20121/4/2012PPART
DetailsMike Jordan
Tim-Screw inspection please Phone #: ###-####. Interior steel studs for bulkheads at sales floor area. Pending electrical rough in inspection.
BLD-Framing/Rough-in12/29/201112/30/201112/30/2011APASS
DetailsJim Storey
TIM Phone #: ###-####perimitor walls ok to cover and compessor rm ok to cover.
BLD-Framing/Rough-in12/29/201112/29/201112/29/2011PPASS
DetailsJim Storey
perimitor walls ok to cover and compessor rm ok to cover.
BLD-Footing12/20/201112/20/201112/20/2011PCANC
DetailsMike Jordan
Tim Phone #: ###-####
BLD-Conference12/20/201112/20/201112/20/2011PDONE
DetailsMike Jordan
Tim Phone #: ###-####. Went over special inspection requirements and general city and code requirements with contractor.