Permit Information
Permit NumberBLD11-02634
StatusFinaled
Name SAM MYERS
Site Address 1116 N COLE RD
Project NameBoise Racquet and Swim Club
Customer Number 
ePlanReviewNo
Description
**(BOISE RACQUET AND SWIM CLUB – Club House)** Application for inspection to determine requirements for issuance of a Certificate of Occupancy for an existing 12,000 square foot club house building. NO NEW WORK IS AUTHORIZED UNDER THIS PERMIT. This tenant space has always been occupied by Boise Racquet and Swim Club. Over the years remodels and additions have been done, but a new C of O addressing the entire building has never been issued. There are no changes to occupancy or use under this permit. TLW
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final6/20/20196/21/20196/21/2019PPASS
DetailsMike Jordan
Ray Phone #: ###-####. OK for perm occ.
FIRE-Final Inspection6/20/20196/21/20196/21/2019APASS
DetailsTroy Cobbley
life safety passed

Ray Phone #: ###-####
BLD-Final12/20/201812/21/201812/21/2018PNR
DetailsMike Jordan
Ray Phone #: ###-####. fire/life/safety has failed.
FIRE-Final Inspection12/20/201812/21/201812/21/2018AFAIL
DetailsJim Page
Numerous escutcheons are missing throughout on the fire sprinkler heads. Fire sprinkler coverage needs to be corrected in womens locker room basement level. Fire sprinklers were added to a closet without a permit. Head coverage issues throughout building, fire sprinkler coverage will need to be corrected under an issued permit, any modifications to the fire sprinkler system requires a p[ermit. Exit signs need serviced throughout. Provide fire sprinkler under HVAC unit in tennis court area. Overhead door on tennis court needs to be measured when open, if door exyends back more than 48 inches then a fire sprinkler will be required.

Ray Phone #: ###-####
FIRE-Final Inspection11/14/201111/15/201111/15/2011AFAIL
DetailsTroy Cobbley
See the upper level and lower level approved floor plans for a list of corrections that need addressed. They include modified sprinkler coverage missing exit signs and missing occupant load sign.