Permit Information
Permit NumberBLD11-02991
StatusFinaled
Name SAUCERMAN CONSTRUCTION
Site Address 9095 S FEDERAL WAY Unit: 104
Project NameKOKUSAI SEMICONDUCTOR
Customer Number 
ePlanReviewNo
Description
(KOKUSAI SEMICONDUCTOR)(SUITE #104) Remodel for a new 1,170 sq. ft. first floor office tenant in vacant shell area within existing 26,000 sq. ft., two story building per approved plans. Shell building was constructed under BLD07-02112. Work to include construction of interior non-bearing walls to define tenant space, interior private office, open office area, accessible compliant break room area, storage and support areas. Walls are to be constructed as indicated on plans by the architect. There is one accessible restroom indicated on plans. Only one is required. Drinking fountain not required. NOTE: This building is fully fire sprinklered for area and story increase. Separate applications, plans, review, approval, and permits are required for sprinkler system work and for alarm system work, all as regulated by the fire department, before work on these items begin. Fire resistive construction is not a code requirement but part of architect design. Building originally reviewed as mixed use non-separated for "B/M/S1" occupancies.drs
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/27/20122/27/20122/27/2012PPASS
DetailsJim Storey
paul - is taking card to ACHD to get signed in time for final inspection Phone #: ###-####
FIRE-Final Inspection2/27/20122/27/20122/27/2012PPASS
DetailsForrest France
Fire life safety inspection completed satisfactory.
FIRE-Alarm Testing2/24/20122/27/20122/27/2012ADONE
DetailsForrest France
Completed testing for the two duct smoke detectors associated with the relocated RTU's.
BLD-Other2/24/20122/24/20122/24/2012PPASS
DetailsJim Storey
Ceiling grid - wall clips corrected / /hvac duct corrected / foam insulation to be removed. Please schedule inspection around 2 - 2:30... Phone #: ###-#### >> Inspection requested via web by Paul Saucerman
BLD-Other2/23/20122/23/20122/23/2012PFAIL
DetailsJim Storey
paul - ceiling grid Phone #: ###-#### missing wall clips/ foam insulation must meet 25/450 or be covered / hvac duct support not to sprinkler line must go to structure.
BLD-Conference2/2/20122/2/20122/2/2012APASS
DetailsJim Storey
call contractor and told him to hold on plm walls plm aproved in error.
BLD-Framing/Rough-in1/31/20122/1/20122/1/2012PPASS
DetailsJim Storey
Rough framing inspection - permit plans on site and code to lock box on door is 1040. Phone #: ###-#### >> Inspection requested via web by Paul Saucerman