BLD-Final | 12/3/2012 | 12/3/2012 | 12/3/2012 | P | PASS |
Jim Storey
|
|
|
Phil Phone #: ###-####
|
FIRE-Final Inspection | 11/26/2012 | 11/27/2012 | 11/27/2012 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
FIRE-Final Inspection | 11/20/2012 | 11/21/2012 | 11/21/2012 | A | FAIL |
Troy Cobbley
|
|
|
All items except for the underground fuel tank sign off (by fire dept.) have been corrected.
|
FIRE-Final Inspection | 10/31/2012 | 10/31/2012 | 10/31/2012 | P | FAIL |
Troy Cobbley
|
|
|
Provide final approval of the underground fuel storage tanks through the Boise Fire Dept., replace all of the painted sprinkler uprights in the wash bay (24 of them) and remove the existing horizontal sidewalls that were left when the overhead doors were removed (they are too far from the deck), reverse door hardware at the passage between the washbay and the shop, provide signage per fire review note #22 at the emergency stop button, provide signage for "partially sprinkler building and zone map" at the fire dept. connection as discussed. Two emergency lights repaired as I waited. Emergency stop of gas pump passed, fire extinguisher at pump as well as signage. Per Romeo Gervais final life safety not to be given until the fire dept. sign off on the fuel tanks. Per Scott Arellano the new additions are not required to have the existing fire protection extended into them.
|
BLD-Framing/Rough-in | 8/20/2012 | 8/20/2012 | 8/20/2012 | P | PASS |
Jim Storey
|
|
|
Jared Phone #: ###-#### heatter support instaled to roof per engineering ok to cover.
|
BLD-Energy code compliance | 7/11/2012 | 7/11/2012 | 7/11/2012 | P | PASS |
Jim Storey
|
|
|
jared Phone #: ###-####
|
BLD-Energy code compliance | 7/2/2012 | 7/2/2012 | 7/2/2012 | P | PASS |
Jim Storey
|
|
|
Jarod Phone #: ###-####
|
BLD-Other | 6/19/2012 | 6/20/2012 | 6/20/2012 | A | PASS |
Jim Storey
|
|
|
phil Phone #: ###-#### canopy ok blots and grout to ft// wall ok to cover upon ele aproval// restarooms ok to cover.
|
BLD-Wall Bracing | 5/31/2012 | 6/1/2012 | 6/1/2012 | P | PASS |
Jim Storey
|
|
|
Phill Phone #: ###-#### roof nailling and straps @48" ok to roof.
|
BLD-Footing | 5/9/2012 | 5/11/2012 | 5/11/2012 | A | PASS |
Jim Storey
|
|
|
Harold- call mins prior for access Phone #: ###-####
|
BLD-Footing | 4/17/2012 | 4/18/2012 | 4/18/2012 | P | PASS |
Tom Arcoraci
|
|
|
Richard Phone #: ###-####
|
BLD-Footing | 4/12/2012 | 4/16/2012 | 4/16/2012 | A | PASS |
Jim Storey
|
|
|
richard Phone #: ###-#### per richard this inspection has nothing to do with the plan mod,ok per Sam Z if plan mod not affected
|