Permit Information
Permit NumberBLD12-00197
StatusFinaled
Name Joe Karpach
Site Address 6455 S EISENMAN RD
Project NameTK BAR
Customer Number 
ePlanReviewYes
Description
(TK BAR) (CUP11-00087) Fire sprinkler system used for story increase and for fire area. To remodel an existing 5,920 square foot building for a new bar tenant to be located on the 2,739 square foot 2nd story. The drinking area will be an A-2 Occupancy and will occupy an area formerly used as a vehicle show room. The floor of the drinking area is a concrete slab on grade. The existing Men’s restroom will be expanded to include a urinal. Work is to include interior nonbearing walls, millwork, and finishes. Two recycling chutes will be provided between the 2nd story and the 1st story. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection4/3/20125/3/20125/4/2012APASS
DetailsForrest France
Final fire life safety inspection passed. Noted correction items have been finished.
BLD-Final5/2/20125/4/20125/4/2012APASS
DetailsMike Jordan
Bruce poe Phone #: ###-####. Ok for perm occ. once life/safety perms.
FIRE-Conference5/2/20125/2/20125/2/2012ADONE
DetailsForrest France
BLD-Final4/2/20124/3/20124/3/2012PPART
DetailsJim Storey
please call 30min prior-- Cory Phone #: ###-#### temp ok pending others.
FIRE-Final Inspection4/2/20124/3/20124/3/2012APART
DetailsForrest France
Temporary occupancy for a period of 30 days approved per R. Gervais. Items for permit final include building service heat at the lower level and a plan modification for the fire alarm system. Location of the remote annunciator was determined acceptable by the Boise Fire Dept.
FIRE-Final Inspection3/30/20124/2/20124/2/2012ANR
DetailsForrest France
Items which remain for final include; door hardware at the main level office, remove surface bolt at the garage area south exit door, provide ceiling at the storage closet main floor, lacking HVAC at the lower level, project related fire alarm permit final pending plan modification.
BLD-Final3/30/20124/2/20124/2/2012PPART
DetailsJim Storey
Bruce Poe-PLease call at least 30 mins prior to inspection Phone #: ###-#### ada vertical grab bars/ signage latch side of doors/ pending fire sign off.
BLD-Final3/29/20123/30/20123/30/2012PCANC
DetailsJim Storey
pm first thing w b poe arch
FIRE-Final Inspection3/27/20123/29/20123/30/2012PFAIL
DetailsForrest France
Project is not ready for fire life safety final due to several items. Project related fire sprinkler and alarm permits need finaled, noted missing hardware at the main entry/exit, need to mount fire extinguishers, post max. occupant load sign, missing ceiling tile, no access at some areas due to floor finishes underway. Building lacks heat at the lower level- unit heaters are missing. Remote annunciator for the fire alarm control panel does not meet location criteria per title 7 section 510.2.
BLD-Final3/27/20123/30/20123/30/2012ADEFR
DetailsJim Storey
Bruce Poe Phone #: ###-####
BLD-Energy code compliance3/26/20123/29/20123/30/2012ADEFR
DetailsJim Storey
bruce ( per Jim Storey 9 am ) Phone #: ###-####
FIRE-Conference3/28/20123/28/20123/28/2012ADONE
DetailsForrest France
Regarding project related FIR permits and schedule for fire life safety inspection items.