BLD-Final | 10/24/2012 | 10/24/2012 | 10/24/2012 | P | PASS |
Jim Storey
|
|
|
Marvin ###-#### p&z n/a final ok
|
FIRE-Final Inspection | 10/24/2012 | 10/24/2012 | 10/24/2012 | P | PASS |
Forrest France
|
|
|
Correction notice items verified for completion. Max occupant sign to be posted as discussed. Fire life safety finaled.
|
FIRE-Final Inspection | 10/23/2012 | 10/24/2012 | 10/24/2012 | A | FAIL |
Troy Cobbley
|
|
|
Provide occupant load sign, provide remote annunciator for the duct smoke detector and provide testing for verification of function or remove duct smoke detector since it is not required per IMC 606, mount the fire extinguisher and provide all city approved drawings for inspection.
|
FIRE-Conference | 10/17/2012 | 10/17/2012 | 10/17/2012 | P | DONE |
Forrest France
|
|
|
bill Phone #: ###-#### Regarding fire life safety inspection items.
|
BLD-Energy code compliance | 9/7/2012 | 9/7/2012 | 9/7/2012 | P | PASS |
Jim Storey
|
|
|
bill Phone #: ###-####
|
BLD-Framing/Rough-in | 9/5/2012 | 9/6/2012 | 9/6/2012 | P | PASS |
Jim Storey
|
|
|
Bill Phone #: ###-####
|
BLD-Conference | 8/22/2012 | 8/22/2012 | 8/22/2012 | P | PASS |
Jim Storey
|
|
|
Bill Petty Phone #: ###-####
|