BLD-Aging Inspection | 5/24/2013 | 5/24/2013 | 5/24/2013 | | PASS |
Mike Jordan
|
|
|
|
BLD-Final | 3/5/2013 | 3/5/2013 | 3/5/2013 | P | PASS |
Mike Jordan
|
|
|
will be ok for perm occ. once zoning signs perm.
|
BLD-Final | 3/4/2013 | 3/5/2013 | 3/5/2013 | A | PEND |
Tom Arcoraci
|
|
|
michael Phone #: ###-#### sent to 450 for pm insp
|
BLD-Final | 2/28/2013 | 2/28/2013 | 2/28/2013 | P | PART |
Mike Jordan
|
|
|
Michael Phone #: ###-####. Ok for temp occ. Needs to complete minor firecaulking on plumbing fixtures.
|
FIRE-Final Inspection | 2/27/2013 | 2/28/2013 | 2/28/2013 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Conference | 2/25/2013 | 2/25/2013 | 2/25/2013 | P | DONE |
Mike Jordan
|
|
|
Michael Phone #: ###-####
|
BLD-Other | 11/2/2012 | 11/5/2012 | 11/5/2012 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Other | 11/2/2012 | 11/2/2012 | 11/2/2012 | P | PASS |
Mike Jordan
|
|
|
Interior shear walls, 1st. flor base layer on horizontal assemblies, face layers at 2nd floor horizontal assemblies.
|
BLD-Energy code compliance | 10/29/2012 | 10/29/2012 | 10/29/2012 | P | PASS |
Tom Arcoraci
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kelly Perryman
|
BLD-Framing/Rough-in | 10/25/2012 | 10/25/2012 | 10/25/2012 | A | PASS |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kelly Perryman. ok to insulate.
|
BLD-Framing/Rough-in | 10/23/2012 | 10/23/2012 | 10/23/2012 | P | PART |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kelly Perryman. Complete all firestopping, brovide blocking for interior shear walls. Still needs fire sprinkler and alarm rough in inspections. No cover at this time.
|
BLD-Framing/Rough-in | 10/19/2012 | 10/19/2012 | 10/19/2012 | P | PART |
Mike Jordan
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kelly Perryman. 1st. floor only, no cover at this time. Fire sprinkler rough in inspection failed. Also noted missing fire caulking for low voltage wiring (fire alarm) unprotected penetration through horizontal asssembly. Contractor to provide approverd UL rated assembly for membrane penetration of bulk wiring through 1hr corridor.
|
BLD-Wall Bracing | 10/5/2012 | 10/5/2012 | 10/5/2012 | P | PASS |
Tom Arcoraci
|
|
|
Phone #: ###-#### >> Inspection requested via web by Kelly Perryman
|