Permit Information
Permit NumberBLD12-00926
StatusFinaled
Name ROCKY MOUNTAIN GROUP INC
Site Address 357 N STEELHEAD WAY
Project NameSCP Sales Center 186
Customer Number 
ePlanReviewYes
Description
(SCP SALES CENTER) To remodel an existing 10,270 square foot office / warehouse tenant space that was created under BLD08-00549. Work is to include: [construction of new interior non-bearing walls to create two offices, open office area, separate sex accessible restrooms, a break room, and a communications room], installation of new lighting, installation of new plumbing, new mechanical ducting (existing RTU’s), and new interior finishes. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection7/23/20127/23/20127/23/2012PPASS
DetailsTroy Cobbley
life safety passed
BLD-Final7/23/20127/23/20127/23/2012PPASS
DetailsMike Jordan
Mic Phone #: ###-####. POK for per occ. once fire/life/safety signs perm.
FIRE-Final Inspection7/20/20127/20/20127/20/2012PFAIL
DetailsTroy Cobbley
The exit signs and emergency lights in the warehouse area need to be finished and tested. Plans need to be resubmitted showing the actual wall layout.
BLD-Final7/20/20127/20/20127/20/2012PFAIL
DetailsMike Jordan
NICK Phone #: ###-####. Needs to submit plan mod showing the deletion of office and double doors. Also needs to have flusher on toilet installed on turning side. Provide special inspection report for racking and calll racking permit in for final. Ceiling grid ok to cover.
BLD-Framing/Rough-in7/2/20127/2/20127/2/2012PPART
DetailsJim Storey
Please call before....... Phone #: ###-#### >> Inspection requested via web by Mick Davis pending ele ri// ok to cover walls upon aproval// c/n isued to have ceilling covered to meet class c smoke/flame spread requirments.
FIRE-Conference6/25/20126/26/20126/26/2012ADONE
DetailsTroy Cobbley
Vic phone #: ###-#### Questions on insulation facing at the deck were deferred to Tim in plan review.
FIRE-Conference6/25/20126/25/20126/25/2012PDONE
DetailsForrest France
Please call prior -- Vic Phone #: ###-#### Conversation with contractor regarding IBC 719.1 and 719.3.