BLD-Final | 8/15/2012 | 8/16/2012 | 8/16/2012 | P | PASS |
Jim Storey
|
|
|
Allen=Please call prior to inspection Phone #: ###-####
|
BLD-Final | 7/27/2012 | 7/30/2012 | 7/30/2012 | P | PART |
Jim Storey
|
|
|
Allen Phone #: ###-#### need smoke seals on doors/ replace door out bldg with out glazing to meet 20 min.
|
FIRE-Final Inspection | 7/25/2012 | 7/26/2012 | 7/27/2012 | A | PASS |
Forrest France
|
|
|
Correction items verified for completion. Fire life safety passed.
|
FIRE-Final Inspection | 7/24/2012 | 7/24/2012 | 7/25/2012 | P | NR |
Forrest France
|
|
|
Pending corrections.
|
FIRE-Final Inspection | 7/20/2012 | 7/23/2012 | 7/23/2012 | A | FAIL |
Forrest France
|
|
|
Noted correction items include; post door to remain unlocked signage at the west main entry/exit doors and remove keyed locking hardware at the first set of vestibule doors, provide approved lever set at the kitchen exit door, relocate fire extinguisher at the second level executive offices to a normal path of travel, post signage at the pool gates, remove keyed lock at the excersise room, post building address numbers as discussed, repair EM lights at four locations. See also list of general requirements attatched to the permit documents for plan review conditions.
|
BLD-Final | 7/20/2012 | 7/23/2012 | 7/23/2012 | P | DEFR |
Jim Storey
|
|
|
Lily Phone #: ###-#### fire c/n listforest call andsaid that they would recall upon completition
|