Permit Information
Permit NumberBLD12-01915
StatusFinaled
Name CHATEAU BUILDERS INC
Site Address 980 N MILWAUKEE ST
Project NameMICKEY RAY'S BBQ RESTAURANT
Customer Number 
ePlanReviewNo
Description
(MICKEY RAY'S BBQ RESTAURANT) This building is fire sprinklered because it has a fire area greater than 5,000 sq. ft.. Permit is to remodel an existing 7,800 square foot restaurant building for a new tenant. This building was constructed and occupied by “Macaroni Grill” under BLD97-01044. Work is to include: construction of new non-bearing partition walls to create a smoker / BBQ room, miscellaneous electrical (no new lighting), miscellaneous mechanical, installation of new accessible doors / hardware, new plumbing, installation of new smoker / BBQ, and interior finishes. . This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final2/6/20132/6/20132/6/2013PPASS
DetailsMike Jordan
rick Phone #: ###-####. Ok for perm occ.
FIRE-Final Inspection2/6/20132/6/20132/6/2013PPASS
DetailsTroy Cobbley
life safety passed
FIRE-Final Inspection11/19/201211/20/201211/20/2012ACANC
DetailsTroy Cobbley
Rick Phone #: ###-####
FIRE-Final Inspection11/19/201211/19/201211/19/2012PCANC
DetailsTroy Cobbley
Cant final the life safety due to issues with the fire alarm permit
BLD-Final11/16/201211/16/201211/16/2012PPASS
DetailsMike Jordan
Rick Phone #: ###-####. signed temp occ. Will be ok for perm occ. once fire/life/safety finals perm.
FIRE-Final Inspection11/16/201211/16/201211/16/2012PPART
DetailsTroy Cobbley
rick - life safety Phone #: ###-#### //temp occ ok, will be ok for perm when fire alarm permit is addressed.
FIRE-Conference11/15/201211/15/201211/15/2012PDONE
DetailsTroy Cobbley
Warren, the electrician, contacted me wanting to know if exit discharge lighting is required. I found that per the building inspectors review notes the exit discharge lights are required.
FIRE-Final Inspection11/13/201211/14/201211/14/2012AFAIL
DetailsTroy Cobbley
The project related fire alarm permit needs finaled. It appears sprinkler protection is needed under the new overhead door at the Smoker. All of the exit signs are non functional. One exit sign needs to be added at the main exit/arch and another at the exit door at the Bar. Repair the non-functional emergency lights. Raise the K class extinguisher in the kitchen to be off the floor. Remove the manaual dead bolt at the freezer door. Provide corrected occupant load sign and contrasting colors for the address numbers.
BLD-Framing/Rough-in11/6/201211/7/201211/7/2012APASS
DetailsTom Arcoraci
rick Phone #: ###-####
FIRE-Conference10/16/201210/16/201210/16/2012PDONE
DetailsTroy Cobbley
I spoke to the general contractor about needing to have the fire alarm system functional before final sign off and that modifications are going to be needed due to the new walls being installed which are blocking the strobe coverage.
BLD-Framing/Rough-in10/4/201210/5/201210/5/2012APEND
DetailsTom Arcoraci
RICK Phone #: ###-####