Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberBLD12-02323
StatusFinaled
Name RRC CONTRACTORS
Site Address 6945 W OVERLAND RD
Project NameD & B SUPPLY
Customer Number 
ePlanReviewNo
Description
(D & B SUPPLY) The fire sprinkler system is used for building area increase and for fire area. To remodel an existing 42,456 square foot tenant space for a new retail tenant. The 2,028 square foot back addition was constructed under permit BLD12-02418. Work is to include interior nonbearing walls, 2 restrooms accessible to the disabled, a roll-up exterior door, exterior concrete stairways and ramp, guards, handrails, suspended acoustical ceilings, display fixtures, and finishes. About 3,350 square feet of roof structure will be removed and replaced with new construction. This will allow the ceiling height to be increased by about 4 feet in that area. Structural work includes new roof beams, new roof joists, and new roof sheathing. New continuous roof insulation (R-20 minimum) and a new TPO roof membrane will be installed above the new roof deck. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final1/15/20131/15/20131/15/2013PPASS
DetailsTom Arcoraci
BRIAN LATE AFTERNOON IF POSSIBLE Phone #: ###-####
FIRE-Final Inspection1/7/20131/8/20131/8/2013APASS
DetailsTroy Cobbley
Life safety passed.
FIRE-Conference12/31/201212/31/201212/31/2012PDONE
DetailsTroy Cobbley
Per Romeo Gervais, with the fire alarm functional, it is ok for the owner to begin stocking the store. Public is not allowed until the fire alarm permit has been finaled and the life safety signed off.
FIRE-Hydro test above ground12/31/201212/31/201212/31/2012PCANC
DetailsTroy Cobbley
Wrong inspection type requested.
BLD-Final12/27/201212/28/201212/28/2012PPEND
DetailsTom Arcoraci
Brian Phone #: ###-#### ok to stock
FIRE-Final Inspection12/27/201212/28/201212/28/2012AFAIL
DetailsTroy Cobbley
Life safety is ok to final when the project related fire alarm permit is passed. Per Romeo it will be ok for the owner to stock if the fire alarm is inspected to verify that sprinkler and hvac monitoring is in place.
BLD-Ceiling Grid Inspection12/18/201212/18/201212/18/2012PPASS
DetailsJim Storey
Brian Phone #: ###-####
BLD-Energy code compliance11/15/201211/16/201211/16/2012APASS
DetailsTom Arcoraci
brian Phone #: ###-####
FIRE-Conference11/15/201211/15/201211/15/2012PDONE
DetailsTroy Cobbley
Per Boise Fire Dept. request I left correction notice requiring the existing FDC at the east wall to meet NFPA 13 requirements for height above access level (18" to 4'). Contractor stated that it will be no problem since a new docking is going to be constructed under it.
BLD-Framing/Rough-in11/8/201211/8/201211/8/2012PPASS
DetailsTom Arcoraci
nailing insp for roof//Derek Phone #: ###-####