Permit Number | BLD12-02938 |
Status | Finaled |
Name |
GUHO CORP
|
Site Address |
1620 W RIVER ST
|
Project Name | Interfaith Sanctuary Housing |
Customer Number | |
ePlanReview | No |
Description |
(INTERFAITH SANCTUARY HOUSING SERVICES - Phased Const.) Records indicate this building is fully sprinklered with NFPA 13 system for an "R1" occupancy use group based on Ch. 9, 2006 IBC and a manual fire alarm system per NFPA 72. This phase of construction involves select interior demolition of non-bearing walls and select interior doors; completing or creating 1-hour fire partitions between sleeping units by use of U.L. Design System U305; installation of accessible transfer shower in existing unisex restroom and an accessible roll-in type shower in conjunction with two regular showers within the existing Men's restroom area; add ceiling access door panel in Men's restroom area; construct new fire partitions to create office 116, and sleeping unit rooms 117, 118 & 119; a new alcoved access/egress door to room 110; new walls and doors to create a utility room off of room 109 for water heater and new floor sink and to separate room 109 from the common 1-hour fire rated corridor exit egress system that serves rooms 105 & 109. The new corridor door is required to be a 20 minute listed & labeled, self-closing, fire / smoke door / frame assembly; all as indicated on plans and in attached plan review comments / conditions of all reviewing agencies as part of the approved plans, requiring code compliance. The upgrade agreement is attached to BLD08-02236. Separate Fire Permits will be required to modify the existing building fire protection systems; as regulated by the Fire Department. drs/srz
|