BLD-Final | 1/30/2013 | 1/30/2013 | 1/30/2013 | P | PASS |
Mike Jordan
|
|
|
HEATH PLEASE CALL 45 MIN BEFORE GOING OUT AS HE IS IN CALDWELL Phone #: ###-####
|
FIRE-Final Inspection | 1/29/2013 | 1/30/2013 | 1/30/2013 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. No materials (gases) are on site for storage arrangement verification.
|
BLD-Conference | 11/29/2012 | 11/30/2012 | 11/30/2012 | A | FAIL |
Mike Jordan
|
|
|
heath Phone #: ###-####. Building is only partiallysprinklered, warehouse only. Resubmit plan to match actual building layout. lever action hardware at exits on warehouse.
|
BLD-Final | 11/29/2012 | 11/30/2012 | 11/30/2012 | A | CANC |
Mike Jordan
|
|
|
will call to set up time, they are in Caldwell//Heath Plaisance Phone #: ###-####
|
FIRE-Final Inspection | 11/29/2012 | 11/29/2012 | 11/29/2012 | P | FAIL |
Troy Cobbley
|
|
|
Resubmit plans to Tim Woodard indicating gas type, quantity and storage arrangement. Resubmit plans showing the actual wall layout (two additional rooms in warhouse). Provide single action hardware on the warehouse exit doors (see IFC 1008.1.9.1). Provide fire extinguishers as discussed. Provide annual inspection for the fire sprinkler system. Repair the fire alarm system and provide a dedicated electrical circuit (see IFC 107.5). Repair the exit signs. Provide knox key box for fire dept access (contact boise fire ###-####). Provide sticker at the main exit "Door to remain unlocked when building is occupied". Contact the boise city fire dept. for operational permit (###-####). Also the building is only partialy sprinklered. The warehouse and outside canopy has sprinkler protection but the office area does not. It appears fire rated doors are installed between the two.
|