BLD-Final | 6/19/2013 | 6/19/2013 | 6/19/2013 | P | PASS |
Tony Young
|
|
|
clint Phone #: ###-####
|
BLD-Final | 6/13/2013 | 6/14/2013 | 6/14/2013 | A | FAIL |
Jim Storey
|
|
|
clint Phone #: ###-#### 1 1/2 at handrail west side of stage so door makes clearance/ block ramp in back on south side exit ramp to the north.
|
BLD-Final | 6/12/2013 | 6/13/2013 | 6/13/2013 | A | NR |
Jim Storey
|
|
|
clint Phone #: ###-#### need mec sign off/ no insp.
|
FIRE-Final Inspection | 6/3/2013 | 6/4/2013 | 6/4/2013 | P | PASS |
Forrest France
|
|
|
Fire life safety inspection completed satisfactory. Noted correction items finished.
|
FIRE-Conference | 5/28/2013 | 5/28/2013 | 5/28/2013 | A | DONE |
Forrest France
|
|
|
Items noted during walkthrough include; building address location, missing exit discharge lighting, missing two exit signs from the kids chruch, missing EM lighting at room 123, door hardware at four breakout rooms and four meeting rooms is non-compliant, repair three EM lights, missing two exit signs at the lobby/lg. meeting room, overspaced fire extinguishers, mechanical mezzanine not shown on plans, missing small documents including the fire code review notes. Need to remove planter at the main entry/exit, post max. occupant load signage per plan annotations.
|
BLD-Final | 5/24/2013 | 5/24/2013 | 5/24/2013 | P | NR |
Mike Jordan
|
|
|
Clint Phone #: ###-####. Needs fire/life/safety finals.
|
FIRE-Conference | 5/23/2013 | 5/23/2013 | 5/23/2013 | A | DONE |
Forrest France
|
|
|
Discussion with contractor regarding fire life safety conditions for final approval, project schedule and related FIR trade work corrections.
|
FIRE-Conference | 5/14/2013 | 5/14/2013 | 5/14/2013 | P | DONE |
Forrest France
|
|
|
Regarding project related FIR trade permit work.
|
BLD-Energy code compliance | 5/13/2013 | 5/13/2013 | 5/13/2013 | P | DONE |
Tony Young
|
|
|
Clint Phone #: ###-####
|
BLD-Energy code compliance | 4/17/2013 | 4/18/2013 | 4/18/2013 | A | PART |
Tony Young
|
|
|
Clint Phone #: ###-####,, bathroom walls ok,, conf on stage frame/insulation/sprinklers,, pending clarification
|
BLD-Energy code compliance | 4/8/2013 | 4/9/2013 | 4/10/2013 | P | PART |
Tony Young
|
|
|
clint Phone #: ###-####,, ok to cover interior walls (steel studs)
|
BLD-Wall cover | 3/21/2013 | 3/22/2013 | 3/22/2013 | A | PART |
Tony Young
|
|
|
Clint Phone #: ###-####,, some interior walls on north side ok for cover,, pending trades
|
BLD-Framing/Rough-in | 3/14/2013 | 3/15/2013 | 3/15/2013 | A | PART |
Tony Young
|
|
|
Clint Phone #: ###-####,, north interior walls ok to insulate,, pending elec. rough pass,,, talked to architect,, he will get as built or change ok for wall types
|