BLD-Final | 4/30/2013 | 5/3/2013 | 5/3/2013 | P | PASS |
Tom Arcoraci
|
|
|
greg Phone #: ###-#### ok for occ no card
|
FIRE-Final Inspection | 4/30/2013 | 5/1/2013 | 5/1/2013 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. Directional arrow on west exit sign needs punched out so people are not led to the locked door prior to the building inspection
|
BLD-Final | 3/15/2013 | 3/20/2013 | 3/20/2013 | A | NR |
Tom Arcoraci
|
|
|
call 1/2 before to meet//Greg Gaddis Phone #: ###-####
|
FIRE-Final Inspection | 3/18/2013 | 3/19/2013 | 3/19/2013 | A | FAIL |
Troy Cobbley
|
|
|
Resubmit plans showing the actual floor layout, repair exit signs and emergency lights, provide emergency lighting in all common paths of egress (if not existing) as discussed, provide fire extinguishers as discussed.
|
FIRE-Final Inspection | 3/15/2013 | 3/18/2013 | 3/18/2013 | P | FAIL |
Troy Cobbley
|
|
|
call 1/2 before to meet//Greg Gaddis Phone #: ###-#### (called and left message just after 1pm, arrived at job at 1:25. Waited until 1:32 and then left. No contact with owner and building is locked.)
|