BLD-Final | 10/15/2014 | 10/16/2014 | 10/16/2014 | A | PASS |
Jim Storey
|
|
|
Odie Phone #: ###-####
|
BLD-Final | 9/16/2014 | 9/17/2014 | 9/17/2014 | A | NR |
Jim Storey
|
|
|
Odie Phone #: ###-####
|
FIRE-Final Inspection | 9/15/2014 | 9/16/2014 | 9/16/2014 | P | PASS |
Forrest France
|
|
|
C/N items completed. Fire life safety passed inspection.
|
FIRE-Final Inspection | 9/3/2014 | 9/4/2014 | 9/4/2014 | A | NR |
Forrest France
|
|
|
Fire life safety final pending project related FIR13-00308.
|
FIRE-Final Inspection | 8/12/2014 | 8/15/2014 | 8/19/2014 | A | PART |
Forrest France
|
|
|
Odie Phone #: ###-####-please give as much notice as possible so he can meet
|
BLD-Framing/Rough-in | 6/23/2014 | 6/24/2014 | 6/24/2014 | A | PASS |
Jim Storey
|
|
|
Odie Phone #: ###-####
|
FIRE-Conference | 5/27/2014 | 5/27/2014 | 5/27/2014 | P | DONE |
Forrest France
|
|
|
Regarding floorplan modifications at the new and existing office areas 1st and 2nd floor.
|
BLD-Framing/Rough-in | 5/13/2014 | 5/14/2014 | 5/14/2014 | A | PASS |
Jim Storey
|
|
|
Odie Phone #: ###-####
|
BLD-Final | 4/17/2014 | 4/18/2014 | 4/18/2014 | A | FAIL |
Jim Storey
|
|
|
Bodie-temp occupancy Phone #: ###-#### door 128 must meet exit door 1008
|
FIRE-Final Inspection | 4/16/2014 | 4/17/2014 | 4/17/2014 | A | PART |
Forrest France
|
|
|
Inspection completed for the new office area addition 1st and 2nd floors. Noted adjustments necessary to exit signage and fire sprinkler coverage. Also completed functional fire alarm testing including occupant notification.
|
BLD-Framing/Rough-in | 12/23/2013 | 12/23/2013 | 12/23/2013 | P | PART |
Jim Storey
|
|
|
Ceiling insepction--Odie Phone #: ###-#### pending others/ vapor barrior at exterior wall at stair.
|
BLD-Framing/Rough-in | 9/16/2013 | 9/17/2013 | 9/17/2013 | P | PASS |
Jim Storey
|
|
|
odie Phone #: ###-#### east exterior wal ok/ interior ok for backing material
|
BLD-Framing/Rough-in | 9/9/2013 | 9/10/2013 | 9/10/2013 | A | PART |
Jim Storey
|
|
|
ernie Phone #: ###-#### exterior walls ok
|
BLD-Framing/Rough-in | 8/22/2013 | 8/23/2013 | 8/23/2013 | A | PART |
Jim Storey
|
|
|
odie Phone #: ###-#### grid 7 exterior wall ok to cover
|
BLD-Conference | 7/10/2013 | 7/10/2013 | 7/10/2013 | A | PART |
Jim Storey
|
|
|
ft and wall performed with si pending reports. contractorto call in for inspection with si requist. si to e-mail reports to 301.
|