BLD-Final | 7/8/2014 | 7/9/2014 | 7/9/2014 | A | PASS |
Mike Jordan
|
|
|
Joe Phone #: ###-####. ok for perm occ.
|
BLD-Footing | 5/29/2014 | 5/30/2014 | 5/30/2014 | A | PART |
Mike Jordan
|
|
|
Joe Phone #: ###-####. Footing inspected by strata. Ok per special inspection report. Verified non shrink grout under column base plates.
|
BLD-Final | 3/10/2014 | 3/11/2014 | 3/11/2014 | A | PASS |
Mike Jordan
|
|
|
joe Phone #: ###-####. Temp occ. given. Will be ok for perm occ. once zoning has signed perm occ.
|
BLD-Final | 3/5/2014 | 3/6/2014 | 3/6/2014 | P | PEND |
Mike Jordan
|
|
|
Joe Phone #: ###-####. Still needs zoning final. Inspection was performed. Needs to add signs to storage racks to read no storage or above 8ft. Everything else ok.
|
FIRE-Final Inspection | 3/5/2014 | 3/6/2014 | 3/6/2014 | A | PASS |
Troy Cobbley
|
|
|
life safety passed. Remove the thumbturn locks at the main exit doors and remove the exit sign as per the aproved plans prior to the building inspection.
|
BLD-Energy code compliance | 12/30/2013 | 12/31/2013 | 12/31/2013 | P | PASS |
Mike Jordan
|
|
|
Joe Phone #: ###-####
|
BLD-Framing/Rough-in | 12/20/2013 | 12/23/2013 | 12/23/2013 | P | PASS |
Mike Jordan
|
|
|
Joe Genovese Phone #: ###-####
|
BLD-Framing/Rough-in | 11/22/2013 | 11/25/2013 | 11/25/2013 | A | PASS |
Mike Jordan
|
|
|
Joe Phone #: ###-####. Exterior wood framed wall over existing concrete double T panels at west wall per RFI from engineer. Ok to cover.
|
BLD-Other | 11/19/2013 | 11/20/2013 | 11/20/2013 | A | PART |
Mike Jordan
|
|
|
roof sheathing - Joseph Phone #: ###-####. Roof sheathing attacment ok. Also noted that a resubmittal is required for the change in exterior wall finishes and framing, no details have been provided.
|
BLD-Footing | 11/12/2013 | 11/13/2013 | 11/13/2013 | A | PASS |
Mike Jordan
|
|
|
joe Phone #: ###-####. footing for new vestibule.
|
BLD-Foundation | 7/24/2013 | 7/25/2013 | 7/25/2013 | P | PART |
Mike Jordan
|
|
|
JOE Phone #: ###-####.
|
BLD-Footing | 7/24/2013 | 7/24/2013 | 7/24/2013 | P | PART |
Mike Jordan
|
|
|
Work in progress. Special inspector wil be on site.
|
BLD-Footing | 7/23/2013 | 7/24/2013 | 7/24/2013 | A | NR |
Mike Jordan
|
|
|
joe Phone #: ###-####. Moved to pm.
|