BLD-Final | 4/1/2015 | 4/1/2015 | 4/1/2015 | P | PASS |
Jim Storey
|
|
|
Request to final per 410- ###-#### All corrections made ok and finaled under FIR14-00142.
|
FIRE-Final Inspection | 4/1/2015 | 4/1/2015 | 4/1/2015 | P | PASS |
Forrest France
|
|
|
Fire life safety finaled.
|
BLD-Final | 12/9/2014 | 12/9/2014 | 12/9/2014 | P | NR |
Jim Storey
|
|
|
Chad Phone #: ###-####
|
BLD-Final | 10/1/2014 | 10/1/2014 | 10/1/2014 | P | DONE |
Jim Storey
|
|
|
All corrections made ok and finaled under FIR14-00142.
|
FIRE-Final Inspection | 5/2/2014 | 5/7/2014 | 5/7/2014 | A | FAIL |
Forrest France
|
|
|
C/N items include; remove keyed locking deadbolts above panic hardware at two locations including the north office area and south breakroom exit doors, post "door to remain...." signage at the main entry/exit, missing fire sprinkler coverage at the fire riser room, need to complete acceptance testing for the building related fire alarm permit work, post signage at the paint booth per fire code review notes.
|
BLD-Final | 5/2/2014 | 5/7/2014 | 5/7/2014 | A | FAIL |
Jim Storey
|
|
|
Chad- Phone #: ###-#### need planreview to resolve missing 1 hr fire wall on plan not in the feild.
|
FIRE-Conference | 5/6/2014 | 5/6/2014 | 5/6/2014 | P | DONE |
Forrest France
|
|
|
Regarding project related fire alarm work.
|
BLD-Conference | 4/16/2014 | 4/16/2014 | 4/16/2014 | A | PART |
Jim Storey
|
|
|
Chcek status? pending fire alarm phone line
|
FIRE-Final Inspection | 12/2/2014 | 12/3/2014 | | A | |
Forrest France
|
|
|
Chad Phone #: ###-####
|