BLD-Final | 10/17/2014 | 10/20/2014 | 10/20/2014 | A | PASS |
Mike Jordan
|
|
|
Thomas Phone #: ###-####. Ok for perm occ.
|
BLD-Final | 10/3/2014 | 10/6/2014 | 10/6/2014 | A | PASS |
Mike Jordan
|
|
|
Call prior to going Phone #: 8016338210 >> Inspection requested via mobile web by Thomas Nielson. ok for perm occ.
|
BLD-Final | 6/26/2014 | 6/27/2014 | 6/27/2014 | A | FAIL |
Mike Jordan
|
|
|
Sanford Phone #: ###-#### or store mngr ###-####. Testing criteria that was submitted does not meet NFPA701 or 289.
|
BLD-Final | 5/2/2014 | 5/5/2014 | 5/5/2014 | P | PART |
Mike Jordan
|
|
|
sanford Phone #: ###-####. Needs flame spread info for decorative trim. ok for temp occ.
|
FIRE-Final Inspection | 5/2/2014 | 5/5/2014 | 5/5/2014 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
FIRE-Final Inspection | 4/30/2014 | 4/30/2014 | 4/30/2014 | P | FAIL |
Troy Cobbley
|
|
|
Provide the third E-stop, permianant mount the E-stop sign, provide additional warning signs at pumps, test the duct smoke detectors, blank the thumbturn lock at the main exit as discussed
|
BLD-Conference | 4/30/2014 | 4/30/2014 | 4/30/2014 | P | DONE |
Mike Jordan
|
|
|
Sanford Phone #: ###-####. Need tactile exit signs at door #1 and #2. Provide smoke and flame spread for trees.
|
BLD-Ceiling Grid Inspection | 3/31/2014 | 3/31/2014 | 3/31/2014 | P | PASS |
Jim Sly
|
|
|
stanford Phone #: ###-####
|
BLD-Energy code compliance | 3/5/2014 | 3/6/2014 | 3/6/2014 | A | PASS |
Mike Jordan
|
|
|
Exterior insulation - Sanford Phone #: ###-####
|
BLD-Energy code compliance | 2/25/2014 | 2/26/2014 | 2/26/2014 | A | PASS |
Mike Jordan
|
|
|
Stanford Phone #: ###-####
|
BLD-Framing/Rough-in | 2/21/2014 | 2/24/2014 | 2/24/2014 | P | PASS |
Mike Jordan
|
|
|
sanford Phone #: ###-####. Ok to insulate exterior walls. Ok to cover interior walls.
|
BLD-Wall Bracing | 2/20/2014 | 2/21/2014 | 2/21/2014 | A | PASS |
Mike Jordan
|
|
|
Water proofing - Sanford Phone #: ###-#### . Remainder of exterior shear walls ok to cover.
|
BLD-Energy code compliance | 2/6/2014 | 2/7/2014 | 2/7/2014 | P | PART |
Jim Sly
|
|
|
Sanford Phone #: ###-#### Walls each side of store front, North 1/4th of East wall, and all of North wall OK to cover. Inspection of approved washers on bolts at bottom wall track......OK.
|
BLD-Framing/Rough-in | 2/5/2014 | 2/6/2014 | 2/6/2014 | P | PART |
Mike Jordan
|
|
|
Partial - Sanford Phone #: ###-####. Exterior shear wall at souh west corner at exterior cooler, interior steel stud framed walls at north wall and partial east wall at interior cooler. Interior cooler portion ok to insulate. Per shear wall notes, needs to provide plate washers at shearwall areas on anchor bolts. Will verify at energy code inspection.
|
BLD-Foundation | 1/10/2014 | 1/13/2014 | 1/13/2014 | A | PASS |
Mike Jordan
|
|
|
foundation insulation - Sanford Phone #: ###-####
|
BLD-Foundation | 1/7/2014 | 1/9/2014 | 1/9/2014 | A | PART |
Mike Jordan
|
|
|
sanford Phone #: ###-####. perimeter stemwalls. Work in progress, pending special inspection.
|
BLD-Footing | 1/2/2014 | 1/6/2014 | 1/6/2014 | A | PASS |
Mike Jordan
|
|
|
sanford PLEASE CALL BEFORE GOING OUT Phone #: ###-####. perimeter footings ok. Will have special inspection. also reviewed all special inspection reports to date for soils. ok.
|