BLD-Final | 4/24/2014 | 4/25/2014 | 4/25/2014 | A | PASS |
Tom Arcoraci
|
|
|
robert Phone #: ###-####
|
DOC - Permit Finaled | 4/25/2014 | 4/25/2014 | 4/25/2014 | P | PASS |
Tom Arcoraci
|
|
|
|
FIRE-Final Inspection | 4/24/2014 | 4/24/2014 | 4/24/2014 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 4/22/2014 | 4/23/2014 | 4/23/2014 | P | NR |
Tom Arcoraci
|
|
|
Jerry Crawford Phone #: ###-####
|
FIRE-Final Inspection | 4/22/2014 | 4/23/2014 | 4/23/2014 | A | FAIL |
Forrest France
|
|
|
HVAC unit did not shut down upon smoke detection. Verified new annunciator and repaired exit signs and emergency lights. Need to remove non-applicable address numbers adjacent to the main entry exit doors.
|
FIRE-Final Inspection | 4/3/2014 | 4/4/2014 | 4/4/2014 | P | FAIL |
Troy Cobbley
|
|
|
Repair the exit sign and the exit discharge lights. One hvac unit has a duct smoke detector that did not shut down the unit upon activation and does not have the required remote annunciator. Fire extinguishers have been mounted.
|
BLD-Final | 1/24/2014 | 1/27/2014 | 1/27/2014 | P | NR |
Tom Arcoraci
|
|
|
Robert Phone #: ###-####
|
FIRE-Final Inspection | 1/27/2014 | 1/27/2014 | 1/27/2014 | P | FAIL |
Troy Cobbley
|
|
|
Provide duct smoke detector and remoter annunciator in hvac unit 5 as per the plans (and test), hvac unit 6 shows a duct smoke detector as well and if installed will need an annunciator and tested too. Also need panic hardware on the two north exits as per the door schedule, need to repair the two exit discharge lights at the north exits and mount the four fire extinguishers as discussed.
|
FIRE-Final Inspection | 1/24/2014 | 1/27/2014 | 1/27/2014 | A | FAIL |
Troy Cobbley
|
|
|
Contractor was not on site and I could not locate any city approved drawings.
|
BLD-Framing/Rough-in | 12/17/2013 | 12/18/2013 | 12/18/2013 | A | PASS |
Tom Arcoraci
|
|
|
Jerry Crawford Phone #: ###-####
|
BLD-Footing | 11/14/2013 | 11/14/2013 | 11/14/2013 | P | PASS |
Tom Arcoraci
|
|
|
|
BLD-Footing | 11/13/2013 | 11/14/2013 | 11/14/2013 | A | PASS |
Tom Arcoraci
|
|
|
jerry Phone #: ###-#### spec insp on site
|