Permit Information
Permit NumberBLD13-02883
StatusIssued
Name CHRIS BOHENKAMP
Site Address 5656 W MORRIS HILL RD
Project NameTreasure Valley Marine
Customer Number 
ePlanReviewNo
Description
(TREASURE VALLEY MARINE)Permit to change existing 52,639 sq foot office, warehouse and distribution to office, warehouse and fabrication. The new tenant will include fabrication of aluminum boats. The area with the change of occupancy is approx. 8,550 sq feet. The office portion of the building had an extensive renovation under BLD10-02521. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **AJS**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection10/28/201310/28/201310/28/2013PPASS
DetailsTroy Cobbley
Life safety passed
BLD-Final10/28/201310/28/201310/28/2013APART
DetailsTom Arcoraci
ok for temp exit sign near wharehouse door to be changed
FIRE-Hydro test above ground10/25/201310/25/201310/25/2013PPART
DetailsCraig D. Hanson
Fire alarm system working and monitored by Alarm Star. Fire sprinklers being inspected and back flow flush by Shilo. Life safety issues OK for temporay CO.
FIRE-Final Inspection10/24/201310/25/201310/25/2013AFAIL
DetailsCraig D. Hanson
met with Chris on site. Fire Alarm and Fire Sprinkler system still needs certification. No apparent modifications to either sstem has been made. Other items: area around all breaker box's need to be cleared. Some exit signs need batteries replaced. HazMat dimond on oil storage tank. Class D extinguisher (1) for welding area. Fuel pump permits being maintaned by other tenant on property. No stotage above wood built structure in bay unless an enginer evaluates. Cooler room being used for boat storage.
FIRE-Final Inspection10/24/201310/24/201310/24/2013PCANC
DetailsTroy Cobbley
Overbooked but Chris and I discussed general life safety requirements on the phone. Per Chris the phone lines for the fire alarm system are being re-installed. I told him that I would need "certification" that the monitoring had been set up and the system tested prior to a final inspection.