Permit Information
Permit NumberBLD13-03479
StatusFinaled
Name STRAIGHT LINE BUILDING SOLUTIONS LL
Site Address 1175 W BOEING ST
Project NameONTRAC
Customer Number 
ePlanReviewNo
Description
(ONTRAC) Fire sprinkler system used for building area increase and for fire area. To remodel a 657 square foot office area and a 2,196 square foot office area located on the 1st story within an existing office/warehouse building having a 62,300 square foot 1st story. About 453 square feet of the existing 2,000 square foot enclosed mezzanine will be occupied as an office. The rest of the mezzanine will not be used. This tenant will occupy the entire building. The existing restrooms are required to be maintained accessible to the disabled. Work is to include interior nonbearing walls, interior windows, interior doors, and interior finishes. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection3/10/20143/10/20143/10/2014PPASS
DetailsForrest France
Remainder of permit work completed and passed fire life safety inspection.
BLD-Final3/10/20143/10/20143/10/2014PPASS
DetailsJim Storey
Call Kelly for Access ###-#### Phone #: ###-#### >> Inspection requested via web by Brian McCoy
BLD-Final2/17/20142/18/20142/18/2014APASS
DetailsJim Storey
Please call Brian McCoy. Lock box code is 1-3-5-9
Asking for a partial so tenant can relocate so work can be completed. Phone #: ###-#### >> Inspection requested via web by Brian McCoy Final pending remainder of remodel work at the SW offices. North office area okayed.
BLD-Final2/17/20142/18/20142/18/2014APASS
DetailsJim Storey
Please call Brian McCoy. Lock box code is 1-3-5-9
Asking for a partial so tenant can relocate so work can be completed. Phone #: ###-#### >> Inspection requested via web by Brian McCoy Final pending remainder of remodel work at the SW offices. North office area okayed.
FIRE-Final Inspection2/17/20142/18/20142/18/2014APART
DetailsForrest France
Final pending remainder of remodel work at the SW offices. North office area okayed.
FIRE-Final Inspection2/12/20142/13/20142/13/2014AFAIL
DetailsForrest France
Items noted include; building address, repair one EM light, post fire extinguisher at the first floor office per plan, install field ceiling tile, provide plan modification reflecting change in work scope (west office remodel NA at this time).
BLD-Framing/Rough-in1/21/20141/22/20141/22/2014APASS
DetailsTony Young
Call Brian McCoy for access.

Lock Box on stair handrail next to front door code is 1-3-5-9 Phone #: ###-#### >> Inspection requested via web by Brian McCoy
BLD-Framing/Rough-in1/20/20141/21/20141/21/2014PDEFR
DetailsJim Storey
Call Brian McCoy for access.

Lock Box on stair handrail next to front door code is 1-3-5-9 Phone #: ###-#### >> Inspection requested via web by Brian McCoy out of time defered to am