Permit Information
Permit NumberBLD14-00342
StatusFinaled
Name CSDI CONSTRUCTION INC
Site Address 4720 N 36TH ST
Project NameQuail Hollow Clubhouse Remodel
Customer Number 
ePlanReviewYes
Description
(QUAIL HOLLOW CLUBHOUSE)This property was annexed in to the City of Boise in 1982. The building was built in 1988. This permit is to remodel the upper level to relocate the pro-shop from the main level to the upper lever. The lower level will be left as is shown on the demo permit for future work to be permitted separately. The upper lever will include minor demo per plans. The existing windows and doors will have structural modifications; the 2 restrooms will be remolded. The kitchen, seating area, food service area will be renovated per approved plans. A new hi/low drinking fountain will be installed. All interior finish material shall meet the requirements of chapter 8 IBC. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **ajs**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Conference8/5/20148/6/20148/6/2014ADEFR
DetailsTony Young
Jeffrey Phone #: ###-####,, address issue,, verify correct ,,, office to handle internally
BLD-Final8/5/20148/6/20148/6/2014ADONE
DetailsTony Young
Jeffrey Phone #: ###-####,, office to handle address issue
BLD-Final8/4/20148/5/20148/5/2014PPASS
DetailsTony Young
Jeffrey Phone #: ###-####
FIRE-Final Inspection8/4/20148/5/20148/5/2014APASS
DetailsTroy Cobbley
Life safety passed per Craig Hansen
BLD-Conference7/24/20147/24/20147/24/2014PPEND
DetailsTony Young
Mike Phone #: ###-####,, walk through for final,, need proper address,, f/l/s
BLD-Final7/18/20147/22/20147/22/2014ACANC
DetailsTony Young
Mike Phone #: ###-####
FIRE-Final Inspection7/18/20147/21/20147/21/2014PFAIL
DetailsCraig D. Hanson
No fire plan review done. Work on hood suppression system done without permit. Hood system not tied into Fire Alarm sytem, permit needed. No Fire Life Safety inspection can be preformed until a hood suppresion permit and fire alarm permit has been issued and finaled. CDH 07/21/14
BLD-Framing/Rough-in6/11/20146/13/20146/13/2014PPASS
DetailsTony Young
mike Phone #: ###-####
FIRE-Conference5/29/20145/29/20145/29/2014PDONE
DetailsForrest France
Discussion with contractor regarding fire sprinkler work, existing cooking hood, scope of remodel, etc.
BLD-Framing/Rough-in5/27/20145/27/20145/27/2014PNR
DetailsJim Storey
Mike Phone #: ###-####