Permit Information
Permit NumberBLD14-01868
StatusFinaled
Name ARBOR FINISH CARPENTRY INC
Site Address 204 N CAPITOL BLVD
Project NameBoise Fry Company-Guru Donuts
Customer Number 
ePlanReviewYes
Description
(BOISE FRY COMPANY / GURU DONUTS – Adelman Building – North side of the 1st Floor) **NO EXTERIOR WORK OF ANY KIND ALLOWED UNDER THIS PERMIT**The fire sprinkler system substitutes for 1-hr fire-resistance-rated construction of the building. To remodel 2,395 square feet of the 1st story for a new restaurant tenant; this tenant also will occupy 2,489 square feet of the basement. A permit to do the work in the basement kitchen was permitted under BLD14-02890 (No occupancy given under that permit). Work is to include: interior nonbearing walls, millwork, seating, walk-in coolers, walk-in freezer, interior doors, two grease hoods and grease ducts, a dishwasher hood and duct, an exterior folding door, structural openings in existing masonry wall, and finishes. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **TLW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection9/8/20169/9/20169/9/2016APASS
DetailsJim Page
Previously noted items have been addressed/repaired. Fire sprinkler inspection is complete, no modifications have been made to the fire alarm system, commercial hood fire suppression system as well as fire extinguisher has current inspection tags. Final life fire safety inspection passed/complete.
FIRE-Final Inspection8/26/20168/26/20168/26/2016PFAIL
DetailsJim Page
Fire plan review documentation was not provided at time of inspection. Fire sprinkler located on the west side of commercial cooking hood is to close, fire sprinkler head needs relocated. Commercial hood fire suppression system did not have a current inspection tag, hood needs to be inspected and tagged. ABC and Class K fire extinguisher needs to be inspected and tagged with current inspection tag, current inspection tags have expired.
BLD-Final8/22/20168/23/20168/24/2016APASS
DetailsDave Hannah
can be done anytime today except 11:30-12:00 that''s lunch rush-if you could, can you do it later so fire can do theres early
FIRE-Final Inspection8/22/20168/23/20168/23/2016ACANC
DetailsJim Page
Spoke with people inside at tenant space, none of the individuals I talked to had any information for a final fire inspection request. No phone name or phone number provided for contact information. Inspection request will need to be rescheduled for another day.
BLD-Final1/8/20151/8/20151/8/2015APART
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Chris Eby ok for temp occ
FIRE-Final Inspection1/8/20151/8/20151/8/2015PPART
DetailsForrest France
Previous C/N items per inspection done 1/6 verified for completion. Temp occupancy approved. Final pending completion of project related FIR trade permit work.
BLD-Final1/7/20151/7/20151/8/2015PNR
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Chris Eby needs other trades to final
FIRE-Final Inspection1/6/20151/7/20151/7/2015AFAIL
DetailsForrest France
Items noted include; trouble condition at the FACP remote annunciator, missing fire sprinkler coverage at the new beer cooler, overspaced sprinkler coverage adjacent to the new cooler, remove keyed lock deadbolt at the basement kitchen exit door, adjust sprinkler coverage at the basement office due to drop ceiling removal.
FIRE-Final Inspection1/6/20151/6/20151/6/2015PNR
DetailsForrest France
Need project related fire sprinkler permit work completion and final prior to BLD fire life safety approval.
BLD-Conference12/28/201412/29/201412/29/2014APASS
DetailsDave Hannah
Look over the framing and drywall for hood shaft. Phone #: ###-#### Inspection requested via web by Chris Eby
BLD-Conference12/23/201412/24/201412/24/2014APASS
DetailsDave Hannah
Look at framing and Sheetrock inside of hood duct shaft. Phone #: ###-#### Inspection requested via web by Chris Eby
BLD-Ceiling Grid Inspection12/23/201412/24/201412/24/2014APASS
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Chris Eby
BLD-Conference12/8/201412/9/201412/9/2014APASS
DetailsDave Hannah
ADA concrete ramps. Phone #: ###-#### Inspection requested via web by Chris Eby
BLD-Other12/3/201412/4/201412/4/2014APEND
DetailsDave Hannah
Inspection for structural steel beams. Phone #: ###-#### Inspection requested via web by Chris Eby need stru engin or spec inspection to sign off
BLD-Ceiling Grid Inspection12/3/201412/4/201412/4/2014APART
DetailsDave Hannah
Phone #: ###-#### Inspection requested via web by Chris Eby needs elec rough ins