FIRE-Final Inspection | 9/8/2016 | 9/9/2016 | 9/9/2016 | A | PASS |
Jim Page
|
|
|
Previously noted items have been addressed/repaired. Fire sprinkler inspection is complete, no modifications have been made to the fire alarm system, commercial hood fire suppression system as well as fire extinguisher has current inspection tags. Final life fire safety inspection passed/complete.
|
FIRE-Final Inspection | 8/26/2016 | 8/26/2016 | 8/26/2016 | P | FAIL |
Jim Page
|
|
|
Fire plan review documentation was not provided at time of inspection. Fire sprinkler located on the west side of commercial cooking hood is to close, fire sprinkler head needs relocated. Commercial hood fire suppression system did not have a current inspection tag, hood needs to be inspected and tagged. ABC and Class K fire extinguisher needs to be inspected and tagged with current inspection tag, current inspection tags have expired.
|
BLD-Final | 8/22/2016 | 8/23/2016 | 8/24/2016 | A | PASS |
Dave Hannah
|
|
|
can be done anytime today except 11:30-12:00 that''s lunch rush-if you could, can you do it later so fire can do theres early
|
FIRE-Final Inspection | 8/22/2016 | 8/23/2016 | 8/23/2016 | A | CANC |
Jim Page
|
|
|
Spoke with people inside at tenant space, none of the individuals I talked to had any information for a final fire inspection request. No phone name or phone number provided for contact information. Inspection request will need to be rescheduled for another day.
|
BLD-Final | 1/8/2015 | 1/8/2015 | 1/8/2015 | A | PART |
Dave Hannah
|
|
|
Phone #: ###-#### Inspection requested via web by Chris Eby ok for temp occ
|
FIRE-Final Inspection | 1/8/2015 | 1/8/2015 | 1/8/2015 | P | PART |
Forrest France
|
|
|
Previous C/N items per inspection done 1/6 verified for completion. Temp occupancy approved. Final pending completion of project related FIR trade permit work.
|
BLD-Final | 1/7/2015 | 1/7/2015 | 1/8/2015 | P | NR |
Dave Hannah
|
|
|
Phone #: ###-#### Inspection requested via web by Chris Eby needs other trades to final
|
FIRE-Final Inspection | 1/6/2015 | 1/7/2015 | 1/7/2015 | A | FAIL |
Forrest France
|
|
|
Items noted include; trouble condition at the FACP remote annunciator, missing fire sprinkler coverage at the new beer cooler, overspaced sprinkler coverage adjacent to the new cooler, remove keyed lock deadbolt at the basement kitchen exit door, adjust sprinkler coverage at the basement office due to drop ceiling removal.
|
FIRE-Final Inspection | 1/6/2015 | 1/6/2015 | 1/6/2015 | P | NR |
Forrest France
|
|
|
Need project related fire sprinkler permit work completion and final prior to BLD fire life safety approval.
|
BLD-Conference | 12/28/2014 | 12/29/2014 | 12/29/2014 | A | PASS |
Dave Hannah
|
|
|
Look over the framing and drywall for hood shaft. Phone #: ###-#### Inspection requested via web by Chris Eby
|
BLD-Conference | 12/23/2014 | 12/24/2014 | 12/24/2014 | A | PASS |
Dave Hannah
|
|
|
Look at framing and Sheetrock inside of hood duct shaft. Phone #: ###-#### Inspection requested via web by Chris Eby
|
BLD-Ceiling Grid Inspection | 12/23/2014 | 12/24/2014 | 12/24/2014 | A | PASS |
Dave Hannah
|
|
|
Phone #: ###-#### Inspection requested via web by Chris Eby
|
BLD-Conference | 12/8/2014 | 12/9/2014 | 12/9/2014 | A | PASS |
Dave Hannah
|
|
|
ADA concrete ramps. Phone #: ###-#### Inspection requested via web by Chris Eby
|
BLD-Other | 12/3/2014 | 12/4/2014 | 12/4/2014 | A | PEND |
Dave Hannah
|
|
|
Inspection for structural steel beams. Phone #: ###-#### Inspection requested via web by Chris Eby need stru engin or spec inspection to sign off
|
BLD-Ceiling Grid Inspection | 12/3/2014 | 12/4/2014 | 12/4/2014 | A | PART |
Dave Hannah
|
|
|
Phone #: ###-#### Inspection requested via web by Chris Eby needs elec rough ins
|