FIRE-Final Inspection | 11/13/2014 | 11/13/2014 | 11/13/2014 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed. Duct smoke detector relocated to return ducting
|
BLD-Final | 11/5/2014 | 11/6/2014 | 11/13/2014 | A | NR |
Jim Sly
|
|
|
MArk Phone #: ###-####
|
BLD-Final | 11/13/2014 | 11/13/2014 | 11/13/2014 | A | PASS |
Jim Sly
|
|
|
Mark ###-####-8573
|
FIRE-Final Inspection | 11/5/2014 | 11/6/2014 | 11/6/2014 | A | FAIL |
Forrest France
|
|
|
AM inspection completed by T. Cobbley- items noted include; provide adequate location for the duct detector or verification min. airflow is met, missing signal transmission to offsite monitoring station, test switch is located at the roof deck.
|
BLD-Final | 11/4/2014 | 11/5/2014 | 11/6/2014 | A | NR |
Jim Sly
|
|
|
Mark Phone #: ###-#### Waiting for fire........
|
FIRE-Final Inspection | 11/4/2014 | 11/5/2014 | 11/5/2014 | A | FAIL |
Troy Cobbley
|
|
|
Contractor was not ready to test the duct smoke detector. Emergency lights have been repaired.
|
BLD-Final | 11/3/2014 | 11/4/2014 | 11/5/2014 | A | CANC |
Jim Sly
|
|
|
Mark Phone #: ###-####
|
FIRE-Final Inspection | 11/3/2014 | 11/4/2014 | 11/4/2014 | A | FAIL |
Troy Cobbley
|
|
|
Not ready due to missing ballasts. Mark is going to reschedule.
|
BLD-Final | 10/31/2014 | 11/3/2014 | 11/3/2014 | P | CANC |
Jim Sly
|
|
|
Mark Phone #: ###-####
|
FIRE-Final Inspection | 10/31/2014 | 11/3/2014 | 11/3/2014 | A | FAIL |
Troy Cobbley
|
|
|
Provide door hardware as discussed, provide fire sprinkler inspection for outstanding permit, provide fire alarm modifications for the duct smoke detectors (see mechanical drawings), repair the emergency lights and provide missing exit sign.
|
BLD-Ceiling Grid Inspection | 10/22/2014 | 10/23/2014 | 10/23/2014 | A | PART |
Jim Sly
|
|
|
Mark Phone #: ###-#### 90 percent complete
|
BLD-Framing/Rough-in | 10/21/2014 | 10/21/2014 | 10/22/2014 | P | PASS |
Jim Sly
|
|
|
mark Phone #: ###-####
|
BLD-Framing/Rough-in | 10/6/2014 | 10/7/2014 | 10/7/2014 | A | PART |
Jim Sly
|
|
|
partial framing // Mark Phone #: ###-#### Long East to West wall, Sm. room at N. E. corner and portions of exterior walls.......OK to cover.
|