BLD-Final | 4/9/2015 | 4/10/2015 | 4/10/2015 | A | PASS |
Jim Sly
|
|
|
Mark Phone #: ###-#### OK for Perm Occ.
|
FIRE-Final Inspection | 4/9/2015 | 4/10/2015 | 4/10/2015 | A | PASS |
Troy Cobbley
|
|
|
life safety passed
|
BLD-Final | 4/3/2015 | 4/6/2015 | 4/6/2015 | P | NR |
Tony Young
|
|
|
Mark Phone #: ###-####
|
FIRE-Final Inspection | 4/3/2015 | 4/6/2015 | 4/6/2015 | A | FAIL |
Troy Cobbley
|
|
|
Need permit showing security tie in with the fire alarm system. Also verification that sensor is not required for the access controled egress door.
|
FIRE-Conference | 2/4/2015 | 2/4/2015 | 2/4/2015 | P | DONE |
Forrest France
|
|
|
On site conference regarding requirements per IFC and IBC related to egress doors equipped with mag lock hardware including; EM lighting, relay to release upon fire alarm or power loss, occ sensor, request to exit button. Also discussed exit signage and locations of fire sprinkler and occupant notification coverage.
|
BLD-Final | 2/3/2015 | 2/4/2015 | 2/4/2015 | A | NR |
Tony Young
|
|
|
Mark Phone #: ###-####,, wanted frame,, not final
|
BLD-Framing/Rough-in | 2/4/2015 | 2/4/2015 | 2/4/2015 | P | PART |
Tony Young
|
|
|
Mark Phone #: ###-####,, door way frame ok pending electrical if needed
|