Permit Number | BLD15-00136 |
Status | Finaled |
Name |
SUNDANCE INVESTMENTS LTD PARTNERS
|
Site Address |
272 N MAPLE GROVE RD
|
Project Name | 8 Feathers Distillery |
Customer Number | |
ePlanReview | No |
Description |
(8 FEATHERS DISTILLERY - Racking) To install steel storage racking exceeding 8' in height within an existing building per approved plans and structural engineering. SPECIAL INSPECTIONS ARE REQUIRED. Work to include: To install 149 square feet total area of racking/shelving. Each unit will be bolted to the floor and have more than 36" isles between rows. The design, testing and utilization of industrial steel storage racks shall be in accordance with the RMI/ANSI MH 16.1. A Letter of Completion is to be issued when done. EACH RACKING SYSTEM SHALL HAVE A PLAQUE LOCATED AT EACH RACKING SYSTEM STATING THE MAXIMUM WEIGHT TO BE STORED ON THAT PERTICULAR RACKING SYSTEM PER THE ENGINEERS CRITERIA STATED ON THE PLANS FOR EACH RACKING SYSTEM. This building is fully Fire Sprinklered for allowable area increase and has an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **SRZ**
|