Permit Information
Permit NumberBLD15-00438
StatusFinaled
Name STENOSCRIBE INC
Site Address 8590 W FAIRVIEW AVE
Project NameHis Way
Customer Number 
ePlanReviewNo
Description
(HIS WAY) Application for inspection to determine requirements for issuance of a Certificate of Occupancy for a 19,376 square foot office and small assembly tenant that will occupy the entire building. This building was formerly used by a private school and office tenant. Most of this building was previously occupied by “Milan Institute”. A Certificate of Occupancy was issued to “Academy of Professional Careers” on May 2, 2001 under permit BLD00-03533. No new work is authorized under this permit. No change of occupancy classification is allowed under this permit. A separate tenant improvement permit is required to create the future toilet/shower room and to change a storage room to an assembly occupancy. The fire sprinkler system is required to be maintained in compliance with NFPA 13 and the fire alarm system is required to be maintained in compliance with NFPA 72 as regulated by the Fire Department. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final3/19/20153/20/20153/20/2015PPASS
DetailsJim Sly
OK for perm. Occ.
FIRE-Final Inspection3/19/20153/20/20153/20/2015APASS
DetailsTroy Cobbley
Life safety passed
BLD-Final3/13/20153/16/20153/17/2015PNR
DetailsJim Sly
Robert Phone #: ###-####
FIRE-Final Inspection3/13/20153/16/20153/16/2015AFAIL
DetailsTroy Cobbley
Still need the fire alarm control panel repaired. It appears that a permit has been submitted for a wireless dialer. Also one exit sign/emergency light failed by Room 119
BLD-Final2/25/20152/27/20152/27/2015PNR
DetailsJim Sly
Rob phone ###-####
FIRE-Final Inspection2/25/20152/26/20152/26/2015AFAIL
DetailsTroy Cobbley
Repair all exit signs and emergency lights, provide annual inspection for fire extinguishers, repair the fire alarm panel, remove interior dead bolts, provide sprinkler modifications where heads are overspaced and provide single action hardware on the exterior exit doors (only one door is allowed to have keyed hardware)
BLD-Final2/24/20152/25/20152/25/2015PNR
DetailsJim Sly
Rob ###-####
Waiting for fire final.
FIRE-Conference2/24/20152/24/20152/25/2015PDONE
DetailsForrest France
BLD-Final2/23/20152/24/20152/24/2015PPART
DetailsJim Sly
Robert Phone #: ###-####
Walk thru with Rob.......Verified that plan matched existing....... waiting for Fire final inspection.
FIRE-Final Inspection2/23/20152/24/20152/24/2015AFAIL
DetailsForrest France
Items noted include; portable fire extinguishers need current certification tags, plans do not match floorplan at some areas, EM lights are not functional at some locations, etc.