BLD-Aging Inspection | 1/28/2016 | 1/28/2016 | 1/29/2016 | | DONE |
Phil Shearer
|
|
|
|
BLD-Final | 1/28/2016 | 1/29/2016 | 1/29/2016 | A | PASS |
Phil Shearer
|
|
|
Please call ahead for acces - Evangeline Phone #: ###-####
|
BLD-Final | 11/19/2015 | 11/20/2015 | 11/20/2015 | P | PART |
Phil Shearer
|
|
|
12:00 - 12:30 Angel// please call before Phone #: ###-####. OK for temp
|
BLD-Final | 11/16/2015 | 11/19/2015 | 11/19/2015 | P | CANC |
Phil Shearer
|
|
|
Angel// please call before Phone #: ###-####
|
FIRE-Final Inspection | 10/19/2015 | 10/20/2015 | 10/19/2015 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed. After repeatly trying to explain about rescheduling this inspection I generated it.
|
BLD-Final | 10/19/2015 | 10/19/2015 | 10/19/2015 | P | NR |
Phil Shearer
|
|
|
Evangeline// please call before Phone #: ###-####
|
BLD-Final | 10/16/2015 | 10/19/2015 | 10/19/2015 | A | FAIL |
Mike Jordan
|
|
|
call for access; Evangeline Phone #: ###-####. Fire/life/safety final failed. Needs to provide code compliant guards and handrails. INstalled hand rails have no extensions and do not return, guard at ramp is not capable of resisting the required 50 pounds per lineal foot applied at any direction.
|
FIRE-Final Inspection | 10/16/2015 | 10/16/2015 | 10/16/2015 | P | FAIL |
Troy Cobbley
|
|
|
Provide single action hardware on the main exit door, remove the thumbturn deadbolt on the rear exit door and provide annual inspection tag for the fire extinguisher. Per plan reviewer the interior door hardware is not required to be upgraded
|