BLD-Final | 4/26/2016 | 4/27/2016 | 4/27/2016 | A | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
FIRE-Final Inspection | 4/25/2016 | 4/25/2016 | 4/25/2016 | P | PASS |
Jim Page
|
|
|
Previously noted items addressed/repaired. Occupancy sign was being printed at time of inspection, will be installed by general contractor. No fire sprinklers, duct detector is stand alone and tested correctly, commercial hood suppression system inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIRE-Final Inspection | 4/22/2016 | 4/22/2016 | 4/22/2016 | P | FAIL |
Troy Cobbley
|
|
|
Rear door exit discharge light can not be connected to a photo cell or timer, duct smoke detector did not shut down the hvac unit upon activation, need occupant load sign at the main exit.
|
FIRE-Final Inspection | 4/1/2016 | 4/4/2016 | 4/4/2016 | A | FAIL |
Troy Cobbley
|
|
|
Can't perform life safety until the project related hood suppression permit is finaled. Per scott and my discussion the new hood and duct smoke detector do not need to be connected to the existing fire alarm system in the day care at the south end of the building due to an existing 4 hour wall that provides separation.
|
BLD-Ceiling Grid Inspection | 3/30/2016 | 3/31/2016 | 4/1/2016 | P | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
BLD-Ceiling Grid Inspection | 2/3/2016 | 2/3/2016 | 2/3/2016 | P | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
BLD-Energy code compliance | 12/16/2015 | 12/17/2015 | 12/17/2015 | P | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|
BLD-Framing/Rough-in | 12/15/2015 | 12/16/2015 | 12/16/2015 | P | PASS |
Jim Storey
|
|
|
Larry Phone #: ###-####
|