BLD-Final | 10/19/2015 | 10/19/2015 | 10/19/2015 | P | PASS |
Dave Hannah
|
|
|
Lisa Phone #: ###-####
|
BLD-Final | 9/17/2015 | 9/18/2015 | 9/18/2015 | P | FAIL |
Phil Shearer
|
|
|
Lisa Phone #: ###-####. storage area as well as the side entrance have twist turn door handles, not paddle type.
|
FIRE-Final Inspection | 9/17/2015 | 9/18/2015 | 9/18/2015 | A | PASS |
Jim Page
|
|
|
Life fire safety passed/complete. Noted that the storage area as well as the side employee entrance have twist turn door handles, not paddle type.
|
BLD-Final | 7/2/2015 | 7/6/2015 | 7/7/2015 | P | NR |
Dave Hannah
|
|
|
Please call ahead 20min to meet - Lisa Phone #: ###-#### needs fire final first
|
FIRE-Final Inspection | 7/2/2015 | 7/6/2015 | 7/6/2015 | A | FAIL |
Jim Page
|
|
|
Fire sprinkler located in the back area of tenant space to far off of wall, head is 9ft 4in, does not meet acceptable spacing requirements for ordinary hazard, 130 square feet per head.
|