BLD-Final | 10/13/2015 | 10/13/2015 | 10/13/2015 | P | PASS |
Jim Sly
|
|
|
Elaina Phone #: ###-#### OK for Perm Occ.
|
FIRE-Final Inspection | 10/13/2015 | 10/13/2015 | 10/13/2015 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 9/4/2015 | 9/4/2015 | 9/4/2015 | P | PART |
Jim Sly
|
|
|
Elaina ###-#### OK for Temp Occ. OK for Perm Occ. when Fire Perms.
|
FIRE-Final Inspection | 9/4/2015 | 9/4/2015 | 9/4/2015 | P | PART |
Jim Page
|
|
|
Previously noted items corrected, TCO authorized for 30 days per conversation with Scott Arellano. Fire alarm alarm system to be repaired/altered on a seperste FIR permit by authorized contractor, TCO contigent on fire alarm permit application/review.
|
BLD-Final | 9/1/2015 | 9/4/2015 | 9/4/2015 | A | CANC |
Jim Sly
|
|
|
Elaina Phone #: ###-####
|
FIRE-Final Inspection | 8/26/2015 | 8/28/2015 | 8/28/2015 | A | FAIL |
Troy Cobbley
|
|
|
Finish construction so the door hardware and new exit signs can be verified, provide permit/work to modify the existing fire alarm system, install smoke alarms as discussed (can be stand alone), provide emergency lighting for the exit path and exit discharge, sprinkler heads in daycare areas need to be quick responce/residential type and provide flash lights for emergency lighting within the day care as discussed. Elaina// please call before Phone #: ###-####
|
FIRE-Final Inspection | 8/26/2015 | 8/26/2015 | 8/26/2015 | P | CANC |
Troy Cobbley
|
|
|
Rescheduled for friday.
|
FIRE-Final Inspection | 8/26/2015 | 8/27/2015 | 8/26/2015 | A | CANC |
Troy Cobbley
|
|
|
To be rescheduled for Friday.
Elaina// please call before Phone #: ###-####
|