Permit Information
Permit NumberBLD15-02257
StatusFinaled
Name MARK HOPKINS
Site Address 7960 W NORTHVIEW ST
Project NameSt. Marks Pre-School
Customer Number 
ePlanReviewYes
Description
(ST. MARK’S PRESCHOOL – SOUTHWEST CORNER OF BUILDING) The fire sprinkler system is used for building area increase. To convert two Church classrooms having a total floor area of about 853 square feet (603 square feet and 250 square feet) to a full-time functioning daycare/preschool within an existing Church. Children less than 2.5 years of age are not allowed to be cared for within the daycare/preschool area since neither of the rooms has a door that opens directly to the outside. Smoke detectors are required in rooms used for sleeping. A carbon monoxide detector is required within each childcare room. The number of children is limited by CUP14-00022 to 24 maximum. Work is to include interior nonbearing walls, 2 egress doors with panic hardware, and exit signs. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such system. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final10/13/201510/13/201510/13/2015PPASS
DetailsJim Sly
Elaina Phone #: ###-####
OK for Perm Occ.
FIRE-Final Inspection10/13/201510/13/201510/13/2015PPASS
DetailsTroy Cobbley
Life safety passed
BLD-Final9/4/20159/4/20159/4/2015PPART
DetailsJim Sly
Elaina ###-####
OK for Temp Occ. OK for Perm Occ. when Fire Perms.
FIRE-Final Inspection9/4/20159/4/20159/4/2015PPART
DetailsJim Page
Previously noted items corrected, TCO authorized for 30 days per conversation with Scott Arellano. Fire alarm alarm system to be repaired/altered on a seperste FIR permit by authorized contractor, TCO contigent on fire alarm permit application/review.
BLD-Final9/1/20159/4/20159/4/2015ACANC
DetailsJim Sly
Elaina Phone #: ###-####
FIRE-Final Inspection8/26/20158/28/20158/28/2015AFAIL
DetailsTroy Cobbley
Finish construction so the door hardware and new exit signs can be verified, provide permit/work to modify the existing fire alarm system, install smoke alarms as discussed (can be stand alone), provide emergency lighting for the exit path and exit discharge, sprinkler heads in daycare areas need to be quick responce/residential type and provide flash lights for emergency lighting within the day care as discussed.
Elaina// please call before Phone #: ###-####
FIRE-Final Inspection8/26/20158/26/20158/26/2015PCANC
DetailsTroy Cobbley
Rescheduled for friday.
FIRE-Final Inspection8/26/20158/27/20158/26/2015ACANC
DetailsTroy Cobbley
To be rescheduled for Friday.

Elaina// please call before Phone #: ###-####