BLD-Final | 12/9/2015 | 12/9/2015 | 12/9/2015 | P | PASS |
Tony Young
|
|
|
would like call ahead; Levi Phone #: ###-####
|
FIRE-Final Inspection | 12/7/2015 | 12/7/2015 | 12/7/2015 | P | PASS |
Jim Page
|
|
|
No fire sprinklers for project, no fire alarms for project. Life fire safety inspection passed/complete.
|
FIRE-Final Inspection | 12/4/2015 | 12/4/2015 | 12/4/2015 | P | CANC |
Jim Page
|
|
|
Inspection cancelled per conversation with Levi, phone number ###-####, will reschedule for later date.
|
FIRE-Final Inspection | 12/2/2015 | 12/3/2015 | 12/3/2015 | A | FAIL |
Jim Page
|
|
|
Door hardware on all doors is of the round knob type, door hardware needs to be changed to single action type door handles. Thumb-turn deadbolt located on west side exit door needs to be removed. Signage reading "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED” needs to be installed on front main entry, tenant is allowed one double keyed deadbolt, currently two deadbolts are installed on front main entry (East side entry). Maximum occupancy sign needs to be installed. City approved plans and small documentation not readily avaiable at time of inspection.
|
BLD-Framing/Rough-in | 11/12/2015 | 11/13/2015 | 11/13/2015 | A | PART |
Dave Hannah
|
|
|
would like call ahead; Levi Phone #: ###-#### ok to cover int framing
|