BLD-Final | 11/17/2017 | 11/17/2017 | 11/17/2017 | P | PASS |
Jim Sly
|
|
|
OK for Perm Occ.
|
BLD-Final | 11/17/2017 | 11/17/2017 | 11/17/2017 | A | CANC |
Jim Sly
|
|
|
Ted 208 440 6227
|
BLD-Final | 11/16/2017 | 11/17/2017 | 11/17/2017 | A | CANC |
Jim Sly
|
|
|
|
BLD-Final | 11/16/2017 | 11/16/2017 | 11/17/2017 | P | CANC |
Jim Sly
|
|
|
Ted Buck Phone #: ###-####
|
DOC - Permit Finaled | | | 11/17/2017 | | DONE |
|
|
|
reference Bld16-01892 for permanent certificate of occupancy
|
BLD-Aging Inspection | 9/7/2017 | 9/7/2017 | 9/14/2017 | | CANC |
Jim Sly
|
|
|
|
BLD-Aging Inspection | 6/28/2017 | 6/28/2017 | 7/6/2017 | | PASS |
Jim Sly
|
|
|
|
BLD-Conference | 2/3/2017 | 2/3/2017 | 2/3/2017 | P | DONE |
Jim Sly
|
|
|
WIP
|
BLD-Aging Inspection | 1/31/2017 | 1/31/2017 | 2/3/2017 | | CANC |
Jim Sly
|
|
|
|
BLD-Final | 12/1/2016 | 12/1/2016 | 12/2/2016 | P | PEND |
Jim Sly
|
|
|
WIP
|
BLD-Aging Inspection | 11/25/2016 | 11/25/2016 | 12/1/2016 | | CANC |
Jim Sly
|
|
|
|
BLD-Conference | 11/30/2016 | 11/30/2016 | 11/30/2016 | P | PEND |
Jim Sly
|
|
|
WIP
|
BLD-Aging Inspection | 9/5/2016 | 9/5/2016 | 9/9/2016 | | CANC |
Jim Sly
|
|
|
|
BLD-Aging Inspection | 7/4/2016 | 7/4/2016 | 7/8/2016 | | CANC |
Jim Sly
|
|
|
|
BLD-Final | 3/9/2016 | 6/10/2016 | 6/10/2016 | A | PEND |
Jim Sly
|
|
|
2nd 90 day extension for Temp occ up. Jason B. OKd temp til 9/4/16.
|
BLD-Conference | 2/12/2016 | 3/10/2016 | 3/10/2016 | A | DONE |
Jim Sly
|
|
|
Check on progress..........Jason B. extended temp for 90 more days.
|
BLD-Aging Inspection | 2/8/2016 | 2/8/2016 | 2/12/2016 | | CANC |
Jim Sly
|
|
|
|
BLD-Final | 12/8/2015 | 12/9/2015 | 12/9/2015 | P | PART |
Jim Sly
|
|
|
Ted Phone #: ###-#### OK for Temp Occ. OK for Perm Occ. When Architect Provides drawings and details for approval on Non complying platform,stairs and handrails located in Sanctuary........and details for missing 2nd handrail on (3) separate stairways to balcony. Provide permit and final inspection for items listed above before 90 day Temp. occ. deadline.
|
FIRE-Final Inspection | 12/8/2015 | 12/9/2015 | 12/9/2015 | A | PASS |
Jim Page
|
|
|
Previously noted items repaired/replaced. Tenant space does have one round type doorknob located in the west side of space, mentioned to Ted the possibility of having to change door knob to paddle type.
|
FIRE-Final Inspection | 11/23/2015 | 11/24/2015 | 11/24/2015 | A | FAIL |
Jim Page
|
|
|
Fire sprinkler system needs to have annual inspection performed, appears last inspection was 2006. Fire alarm system needs to have annual inspection performed. Fire extinguishers are current for inspection, all exit lights and emergency egress lighting needs to be serviced/repaired. Covers on numerous electrical outlets missing, need to be in place for next inspection, electrical outlets on upper mezzanine in chapel area need to be re-installed into electrical boxes in the floor, currently out of the boxes with exposed wires.
|
BLD-Final | 11/23/2015 | 11/24/2015 | 11/24/2015 | P | CANC |
Jim Sly
|
|
|
Call half hour before to meet // Ted Phone #: ###-####
|