BLD-Final | 7/12/2016 | 7/13/2016 | 7/13/2016 | A | PASS |
Dave Hannah
|
|
|
Larry Phone #: ###-####
|
FIRE-Final Inspection | 7/12/2016 | 7/13/2016 | 7/13/2016 | A | PASS |
Jim Page
|
|
|
Previously noted issue with fire sprinklers repaired, fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers in common area's with current inspection tags. Final life fire safety inspection passed/complete.
|
BLD-Final | 7/5/2016 | 7/7/2016 | 7/8/2016 | P | PART |
Dave Hannah
|
|
|
Phone #: ###-#### ok for temp occ
|
FIRE-Final Inspection | 7/6/2016 | 7/7/2016 | 7/7/2016 | A | PART |
Jim Page
|
|
|
Fire sprinkler inspection is complete (Cabinet that was installed after the sprinkler inspection is to close to the fire sprinkler, cabinet will need to be altered to clear 18 inches below deflector or fire sprinkler head will need to be relocated), fire alarm inspection is complete, fire extinguishers are in place with current inspection tags. Partial life fire safety inspection complete excluding the fire sprinkler head above cabinet which will be inspected when complete
|
BLD-Ceiling Grid Inspection | 6/7/2016 | 6/7/2016 | 6/7/2016 | P | PASS |
Dave Hannah
|
|
|
Kevin Phone #: ###-####
|
BLD-Framing/Rough-in | 5/19/2016 | 5/20/2016 | 5/20/2016 | A | PASS |
Bob Archibald
|
|
|
Phone #: ###-#### Inspection requested via web by Todd Landvatter. Interior nonbearing walls at west entrance approved for cover.
|
BLD-Framing/Rough-in | 3/29/2016 | 3/30/2016 | 3/30/2016 | A | PASS |
Dave Hannah
|
|
|
construction door by Utility Billing entrance. lock code is 1512. Phone #: ###-#### Inspection requested via web by Todd Landvatter walls only
|