BLD-Final | 10/24/2016 | 10/25/2016 | 10/25/2016 | P | PASS |
Jim Sly
|
|
|
Adam Phone #: ###-####
|
FIRE-Final Inspection | 10/24/2016 | 10/25/2016 | 10/25/2016 | A | PASS |
Troy Cobbley
|
|
|
Life safety passed
|
BLD-Final | 10/20/2016 | 10/21/2016 | 10/21/2016 | P | NR |
Jim Sly
|
|
|
Adam-as early as possible Phone #: ###-#### Need Fire insp.
|
FIRE-Final Inspection | 10/20/2016 | 10/21/2016 | 10/21/2016 | A | FAIL |
Troy Cobbley
|
|
|
I went to the job site twice, called six times and left three voice messages but could not make contact. I noted that not all work was done such as exit from Patio, panic hardware at both main exit doors or exit discharge lighting at both main exit doors.
Adam-as early as possible Phone #: ###-####
|
BLD-Conference | 10/18/2016 | 10/18/2016 | 10/18/2016 | P | FAIL |
Jim Sly
|
|
|
Adam Phone #: ###-#### Provide code complying egress out of exterior patio area.
|
FIRE-Final Inspection | 10/17/2016 | 10/18/2016 | 10/18/2016 | A | FAIL |
Troy Cobbley
|
|
|
Provide exit signs with battery backup at all three doors per the approved plans, provide emergency lighting per the approved plans, provide panic hardware as per the approved plans, provide corrected occupant load sign, provide exit discharge emergency lighting per review note #6, provide code compliant exit from the Patio per the review comments, provide ADA approved hardware for the Office door.
|