Information based on query as of Wednesday, June 26, 2024.
Permit Information
Permit NumberBLD17-00149
StatusIssued
Name RAISTRICK CONSTRUCTION
Site Address 2323 S VISTA AVE Unit: 100 & 101
Project NamePets Best Inc.
Customer Number 
ePlanReviewYes
Description
(PETS BEST INC. – Vista / Targee Building – Ste# 100 &101) Permit is to remodel three existing suites for use by one tenant. Work will include adding interior non-loadbearing walls to create three new offices and removal of interior walls to create a more open floor plan. Also, reverse the door swing from suite D that leads into the corridor. This building is sprinklered for area increase. Approval contingent upon adhering to the approved plans on file. This building is fully fire sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **DAF**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final4/18/20174/21/20174/21/2017ACANC
DetailsJim Storey
Tom Phone #: ###-####
BLD-Final4/20/20174/21/20174/21/2017PPART
DetailsJim Storey
please call before to meet // Tom Phone #: ###-#### A temporary occupancy is being given. While testing the fire alarm system modifications I noted that there are two different temporal cadences and solid tone horns all going at the same time. This is in both the tenant areas and the common/egress/core areas of the building which may include the second floor which is accessable by an open stair well. All notification devices are to sync both visually and audibly. This condition needs to be repaired or an upgrade agreement sought with the Boise Fire Dept as discussed. final ok for l/c pending fire sign off.
FIRE-Final Inspection4/20/20174/21/20174/21/2017APART
DetailsTroy Cobbley
A temporary occupancy is being given on the life safety until the project related fire alarm permit is addressed. While testing the fire alarm system modifications I noted that there are two different temporal cadences and solid tone horns all going at the same time. This is in both the tenant areas and the common/egress/core areas of the building which may include the second floor which is accessable by an open stair well. All notification devices are to sync both visually and audibly. This condition needs to be repaired or an upgrade agreement sought with the Boise Fire Dept as discussed.
FIRE-Final Inspection4/18/20174/20/20174/20/2017PFAIL
DetailsTroy Cobbley
I stopped at the project site to make contact with the contractor but could not find anyone. All doors are electronically secured. I did speak to a Pets Best representative but his supervisor was not in. No inspection performed. Tom Phone #: ###-####
BLD-Framing/Rough-in4/5/20174/5/20174/5/2017PPASS
DetailsJim Storey
Tom-ste 100 AND 101-knock on wimdow and someone will let you in Phone #: ###-####