Permit Information
Permit NumberBLD17-00374
StatusFinaled
Name HCD INC
Site Address 6633 S FEDERAL WAY
Project NamePeterbilt Code Compliance
Customer Number 
ePlanReviewYes
Description
(PETERBUILT)** Permit to show code compliance in order to obtain a Certificate of Occupancy for an existing 17,830 sq. ft. building that is currently occupied by Peterbuilt. County records indicate that this building was constructed in ADA County in 1976 therefore the neither the City of Boise or the county have drawings for the building. There is record of an inspection performed by a city inspector and a plan reviewer that states that several code violations inside the building such as occupancy separation between the office areas and the warehouse. Also, in speaking with the inspector, he informed me that he also observed that the 2nd floor storage racking system appeared to have been constructed after the original construction of the building and is a metal grid system where portions rest on a non-structural rack system below with suspension cables that also attach to the roof rafters above. Any future additions to the repair portion of this building will required the addition if a NFPA 13 sprinkler system. This building is not fire sprinklered. The existing racking system will be addressed at a later date and is not approved under this permit. CDM
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/27/201812/28/201812/28/2018PPASS
DetailsJim Storey
Please call Dutch 30 minutes prior to arrival thank you Phone #: ###-#### Inspection requested via web by Dennis Harmon final ok wrong card need c.o. per plan reviewer insp. card and lc will not achive this requirment. 301
BLD-Final12/21/201812/24/201812/24/2018AFAIL
DetailsJim Storey
Please call Dutch one hour prior to arrival Thank You Phone #: ###-#### Inspection requested via web by Dennis Harmon counter arch to resolve work space to not impeed with fire shudder/ need listing for 45 min door closers.
FIRE-Final Inspection12/20/201812/21/201812/21/2018PPASS
DetailsJim Page
Previously noted iyems have been corrected, final life fire safety inspection for area of work complete.

Have scheduled door company for a 1:00pm drop test on coil door if any questions please call Dutch @ 208 249 6313 Thank you Phone #: ###-#### Inspection requested via web by Dennis Harmon
BLD-Aging Inspection10/5/201810/5/201810/5/2018 PASS
DetailsJim Storey
5/23/2018 5/24/2018 5/24/2018 A FAIL





DetailsTroy Cobbley

Repair main entrance exit discharge light, Provide panic hardware on door 111A, Provide listed smoke detectors, both sides, for release of door. See NFPA 72 17.7.5.6 for door 113A, Provide installation and testing of roll down fire door per NFPA 80, Provide exit sign/emergency llight and single action hardware at door 116A, Provide revised floor plans showing revised wall layout at doors 113A and 116A, Provide emergency lighting at interior west stairs as shown on the plans, Remove dead bolts from doors 119A, 119B and 115B, Provide racking permit for storage racks exceeding 8'-0" in height, Provide list of type/quantity of hazardous chemicals such as oil storage (new & waste), parts solvents, batteries...ect.
FIRE-Final Inspection5/23/20185/24/20185/24/2018AFAIL
DetailsTroy Cobbley
Repair main entrance exit discharge light, Provide panic hardware on door 111A, Provide listed smoke detectors, both sides, for release of door. See NFPA 72 17.7.5.6 for door 113A, Provide installation and testing of roll down fire door per NFPA 80, Provide exit sign/emergency llight and single action hardware at door 116A, Provide revised floor plans showing revised wall layout at doors 113A and 116A, Provide emergency lighting at interior west stairs as shown on the plans, Remove dead bolts from doors 119A, 119B and 115B, Provide racking permit for storage racks exceeding 8'-0" in height, Provide list of type/quantity of hazardous chemicals such as oil storage (new & waste), parts solvents, batteries...ect.


please call Dutch @###-#### 1 hr before arrival, Thank you Phone #: ###-#### Inspection requested via web by Dennis Harmon
BLD-Framing/Rough-in2/25/20182/26/20182/26/2018APASS
DetailsJim Storey
Please call Dutch 1/2 hour prior to arrival thank you Phone #: ###-#### Inspection requested via web by Dennis Harmon 2nd floor north end fire wall ch studs and core board ok fire stopping insided wall on shop side.
BLD-Conference12/8/201712/11/201712/11/2017ADONE
DetailsJim Storey
Please call Dutch 45 minutes prior to arrival thank you Phone #: ###-#### Inspection requested via web by Dennis Harmon need info floor bearing on rated wall/ radted counter tag and listing/ girt and purlins fire stopping aproval// hvac protections// no spk hourly rating on wall .