Information based on query as of Friday, June 28, 2024.
Permit Information
Permit NumberBLD17-00445
StatusFinaled
Name TIM BERGEY CONSTRUCTION
Site Address 705 W FULTON ST
Project NameWhite Dog Brewery TI
Customer Number 
ePlanReviewYes
Description
(WHITE DOG BREWERY) Permit for tenant improvement work includes relocating lighting, two new doors, placing plumbing fixtures at existing hook-ups, new finishes and furniture, relocating sprinkler heads, no mechanical or exterior work on the building. Core and shell permitted under BLD16-03811. This building is fully Fire Sprinklered with an approved Fire Alarm system. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **ajs**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final8/7/20178/7/20178/7/2017PPASS
DetailsBrandon Shaw
Dan Phone #: ###-####
DOC - Permit Finaled8/7/20178/7/20178/7/2017PPASS
DetailsBrandon Shaw
FIRE-Final Inspection8/4/20178/7/20178/7/2017APASS
DetailsJim Page
Previously noted items have been repaired. Fire sprinkler inspection complete, no fire alarm modifications, fire extinguishers are in place. Final life fire safety inspection passed/complete.
BLD-Final7/28/20177/31/20178/4/2017APEND
DetailsDave Hannah
Here you go Dave. Thanks. Plumbing, Electrical, and FLS are done. Phone #: ###-#### Inspection requested via web by Tim Bergey ok after fire finals
FIRE-Final Inspection8/1/20178/2/20178/2/2017PCANC
DetailsJim Page
Duplicate inspection request, this inspection request for fire life safety is cancelled
FIRE-Final Inspection8/1/20178/2/20178/2/2017AFAIL
DetailsJim Page
1. Escutcheon in southwest cooler missing on dry pendant.
2. Exit discharge landing light on northwest exit did not illuminate when test button was pushed.
3. Emergency lighting in seating area and west hall not operational.
4. West emergency exit does not have discharge landing egress lighting installed, discharge landing emergency egress lighting needs to be installed.
5. Exit sign needs to be installed in south brewing area above south door leading to designated exterior ext in storage area.
6. Exit sign/emergency lighting needs to be installed in south storage area to include exit discharge landing illumination.
7. No fire extinguishers installed at time of inspection.
BLD-Final7/25/20177/25/20177/28/2017PNR
DetailsDave Hannah
Please call Dan if needed. I am out of town. Thanks Dave! Phone #: ###-#### Inspection requested via web by Tim Bergey needs plumbing final