BLD-Final | 11/8/2017 | 11/9/2017 | 11/9/2017 | P | PASS |
Tony Young
|
|
|
Troy Phone #: ###-####
|
FIRE-Final Inspection | 11/8/2017 | 11/9/2017 | 11/9/2017 | A | PASS |
Jim Page
|
|
|
Fire sprinkler inspection complete, fire alarm inspection complete (FIR17-00569), commercial hood fire suppression system inspection complete (FIR17-00403), fire extinguishers are in place with current inspection tags, knox box is located by main entry. Final life fire safety inspection passed/complete.
|
FIRE-Final Inspection | 11/3/2017 | 11/6/2017 | 11/6/2017 | P | FAIL |
Troy Cobbley
|
|
|
Per the mechanical prints two duct smoke detectors are required. They were not addressed with the fire alarm permit which has been finaled. A new permit is needed.. Address numbers on both sides of the building are needed as well.
Troy Phone #: ###-####
|
BLD-Ceiling Grid Inspection | 10/19/2017 | 10/19/2017 | 10/19/2017 | P | PASS |
Tony Young
|
|
|
Troy Phone #: ###-####
|
BLD-Framing/Rough-in | 9/11/2017 | 9/11/2017 | 9/12/2017 | P | PASS |
Tony Young
|
|
|
Troy Phone #: ###-####,, int walls
|
BLD-Energy code compliance | 9/8/2017 | 9/11/2017 | 9/11/2017 | A | PART |
Tony Young
|
|
|
Troy Phone #: ###-####,, exterior walls ok,,
|
BLD-Framing/Rough-in | 9/8/2017 | 9/8/2017 | 9/8/2017 | P | NH |
Tony Young
|
|
|
Troy Phone #: ###-####
|