BLD-Final | 5/18/2017 | 5/19/2017 | 5/19/2017 | P | PASS |
Dave Hannah
|
|
|
Dustin Phone #: ###-####
|
FIRE-Final Inspection | 5/18/2017 | 5/19/2017 | 5/19/2017 | A | PASS |
Jim Page
|
|
|
Previously noted items have been addressed, escutchions for fire sprinkler heads will be installed before final builing inspection. Final life fire safety inspection passed/complete
|
FIRE-Final Inspection | 5/10/2017 | 5/10/2017 | 5/10/2017 | P | FAIL |
Jim Page
|
|
|
Exit sign located above south exit needs to be serviced, hood suppression system needs to be serviced/inspected and tagged before final life fire safety inspection, class K fire extinguisher needs to be inspected/serviced and a current inspection tag placed, fire extinguisher with a current inspection tag needs to be installed in seating area, existing grill tops that will be used for seating need to be disconnected from energy source (gas and or electrical power), surface mount slide bolt locks on northeast interior door needs to be removed, padlock clasp on interior office door needs to be removed, signage for exterior gate needs to be installed reading "Gate to remain unlocked while occupied" per approved drawings note, fire sprinkler head next to northwest door needs to be replaced due to excessive external loading, missing escutcheons need to be installed on fire sprinkler heads.
|