Permit Information
Permit NumberBLD17-01548
StatusIssued
Name ZELHAM INC
Site Address 5257 W FAIRVIEW AVE
Project NameZelham Offices - Remodel
Customer Number 
ePlanReviewYes
Description
(ZELHAM OFFICES – 1ST STORY) The fire sprinkler system is used in lieu of rated corridors. A fire sprinkler system will be installed throughout the 1st story in conjunction with this permit. A fire sprinkler system will be installed throughout the 2nd story under a future phase. To remodel the entire 13,988 square foot 1st story of an existing two story building which includes five areas (1) 5,481 square foot office tenant space with 55 OL in the East end of the building, (2) 2,604 square foot office tenant space with 26 OL in the Northwest corner of the building, (3) 1,653 square foot shell tenant space with 17 OL in the Southwest corner of the building, (4) 668 square foot fitness room / break room / server with 25 OL, and (5) 538 square foot shared conference room with 36 OL. To expand the existing Men’s common restroom on the 1st story by 102 square feet to 266 square feet (add 3 toilets) and to expand the existing Women’s common restroom on the 1st story by 102 square feet to 264 square feet (add 3 toilets). A new doorway will be created in an existing masonry wall between the existing restrooms and the restroom expansion areas. Steel headers and steel jambs will be installed. Work is to include interior nonbearing walls, a new toilet / shower room accessible to the disabled, interior doors, interior windows, millwork, and finishes. The work is required to comply with the approved drawings, with the structural details, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. A fire sprinkler permit and a fire alarm permit shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection5/15/20185/15/20185/15/2018PPASS
DetailsJim Page
Final life fire safety inspection complete.

2nd Floor reception door mag lock replaced with electric strike Phone #: ###-#### Inspection requested via web by Steve Jones
BLD-Final3/19/20183/19/20183/20/2018PPART
DetailsJim Sly
Phone #: ###-#### Inspection requested via web by Steve Jones
OK for Temp. Occ. See previous Fire inspectors notes.
FIRE-Final Inspection3/16/20183/19/20183/19/2018APART
DetailsTroy Cobbley
A temporary for life safety is being given with Assistant Chief Ron's permission until the two pre-action systems/rooms have been addressed. Per the contractor the smoke detectors are active in these rooms. They will need to remain active until the associated pre-action system is functional.
FIRE-Conference2/1/20182/1/20182/1/2018PDONE
DetailsTroy Cobbley
We discussed life safety items such as possible exit discharge lighting and interconnection of the access control egress locks with the new fire alarm system
BLD-Wall cover12/20/201712/20/201712/20/2017PPASS
DetailsJim Sly
Inspection requested via web by Steve Jones
BLD-Framing/Rough-in11/22/201711/22/201711/22/2017PPASS
DetailsMike Jordan
Northeast quadrant offices. Phone #: ###-#### Inspection requested via web by Steve Jones. North west wing interior steel stud framed walls ok. Hard lid in main lobby ok, pending lectrical and fire .
BLD-Framing/Rough-in11/16/201711/16/201711/16/2017PPASS
DetailsJim Sly
1st Floor East of Lobby Phone #: ###-#### Inspection requested via web by Steve Jones