BLD-Conference | 8/25/2017 | 8/25/2017 | 8/25/2017 | P | CANC |
Mike Jordan
|
|
|
|
BLD-Final | 8/24/2017 | 8/25/2017 | 8/25/2017 | A | PASS |
Mike Jordan
|
|
|
call half hour before// Kevin Phone #: ###-####. Ok for perm occ.
|
BLD-Final | 8/23/2017 | 8/24/2017 | 8/24/2017 | A | NR |
Mike Jordan
|
|
|
Call half hour before // Kevin Phone #: ###-####. No access. Will reschedule.
|
FIRE-Final Inspection | 8/22/2017 | 8/23/2017 | 8/23/2017 | P | PASS |
Troy Cobbley
|
|
|
Life safety passed.
Kevin Phone #: ###-####
|
FIRE-Final Inspection | 8/8/2017 | 8/9/2017 | 8/9/2017 | P | FAIL |
Troy Cobbley
|
|
|
Need project related fire alrm permit finaled, provide sign for Riser Room and mount the third fire extinguisher as discussed.
|
FIRE-Final Inspection | 8/3/2017 | 8/4/2017 | 8/4/2017 | A | CANC |
Troy Cobbley
|
|
|
Please contact Kevin Staats for Access 30min Prior ###-#### Phone #: ###-#### Inspection requested via web by Brian McCoy
|
FIRE-Conference | 7/28/2017 | 7/28/2017 | 7/28/2017 | P | DONE |
Jim Page
|
|
|
Fire conference is complete, exit discharge emergency lighting needs to be installed on the designated exterior exits on the west side exit in the warehouse and southeast exit (main entry into the office area). Current address on building reads 2701B, permit has the address as 2707, address needs to be verified and the correct numbering needs to be installed. There is an open FIR permit associated with this building permit, FIR17-00392 permt needs to be inspected and passed before life fire safety can be completed. The fire alarm system will be monitored when complete, the building currently does not have a knox box, a knox box needs to be installed before final life fire safety inspection.
|
FIRE-Final Inspection | 7/28/2017 | 7/28/2017 | 7/28/2017 | P | CANC |
Jim Page
|
|
|
Inspection request is for a life fire safety conference, this inspection request is cancelled.
|