Permit Information
Permit NumberBLD17-02486
StatusFinaled
Name JORDAN WILCOMB CONSTRUCTION
Site Address 7590 W VICTORY RD
Project NameCurtis Restaurant Equipment
Customer Number 
ePlanReviewYes
Description
(CURTIS RESTAURANT EQUIPMENT – EAST END OF BUILDING) (CZC17-00204) The fire sprinkler system is used for building area increase and for fire area. To create a 12,181 square foot sales and warehouse tenant space within a new 21,885 square foot building. The building shell was constructed under permit BLD17-00763. Work is to include a tenant demising wall, interior nonbearing walls, two toilet rooms accessible to the disabled, a new double leaf exterior door, exterior wall infills, suspended acoustical ceilings, gypsum board ceilings, millwork, and finishes. A separate racking permit is required for racks more than 8 feet tall. The future test kitchen will be done under a separate permit. The work is required to comply with the approved drawings, with the plan review report, and with all applicable codes and ordinances. The fire sprinkler system is required to comply with NFPA 13 and the fire alarm system is required to comply with NFPA 72 as regulated by the Fire Department. Separate fire sprinkler permits and fire alarm permits shall be obtained prior to beginning any modification or installation work on such systems. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
BLD-Final12/26/201712/27/201712/27/2017PPASS
DetailsMike Jordan
Door glass installed. Phone #: ###-#### Inspection requested via web by Mark Steen. Ok for perm occ.
BLD-Final12/11/201712/12/201712/12/2017PPART
DetailsMike Jordan
Troy to re-inspect doors and lights in the AM for fire life safety final, will pass the word whether we pass or fail. Thanks Phone #: ###-#### Inspection requested via web by Mark Steen. Ok for temp occ. nneds to install tempered glazing in doors and provide transition from offices.
FIRE-Final Inspection12/11/201712/12/201712/12/2017APASS
DetailsTroy Cobbley
life safety passed
BLD-Final12/7/201712/8/201712/8/2017PNR
DetailsJim Sly
Please note that a re-inspection for life safety was requested for AM. Also note that final electrical is scheduled for AM. Also refer to BLD17-00763 which is the same building and is also a PM Final. Allowing one visit on two Finals. Thanks, Mark Steen Phone #: ###-#### Inspection requested via web by Mark Steen
Need fire final.......shell/core finaled.
FIRE-Final Inspection12/7/201712/8/201712/8/2017ACANC
DetailsTroy Cobbley
Not ready for final. Will be rescheduled for tuesday

Please note that a call to Carl Westfall about the door egress issue is awaiting a reply. Also The Exit Discharge lights will not be on the timer system any longer. Thanks, Mark Steen Phone #: ###-#### Inspection requested via web by Mark Steen
FIRE-Final Inspection12/6/201712/7/201712/7/2017PFAIL
DetailsTroy Cobbley
Provide correct hardware on all exit doors as discussed or provide plan review approval that they can be turned into windows by having hardware and exit signs removed. Exit discharge lights appear to be on a timer which is not allowed. provide missing exit sign at the north east exit door
BLD-Framing/Rough-in10/30/201710/31/201710/31/2017APASS
DetailsMike Jordan
Follow up, see notes from previous Insp of Oct 27.
Thanks, Mark Steen Phone #: ###-#### Inspection requested via web by Kareen Falls. All trades have signed off.
BLD-Framing/Rough-in10/26/201710/27/201710/30/2017PPART
DetailsBrandon Shaw
OK to cover one side, pending other trades