Permit Information
Permit NumberBLD17-03045
StatusFinaled
Name BRIGHT STAR ENERGY MANAGEMENT LLC
Site Address 7709 W OVERLAND RD Unit: STE 100
Project NameBoise Barber College
Customer Number 
ePlanReviewYes
Description
(BOISE BARBER COLLEGE - THE BOISE SPECTRUM - BUILDING B - SUITE 100) This building is fire sprinklered for building area increase. Permit is to remodel an existing 9,489 sq. ft. hairdressing salon/college space. Approval is contingent upon adhering to the approved plans on file. Work to include: removal of select walls, removal of select millwork, relocation of select floor drains, construction of interior non-bearing walls to create a hall leading to existing storage area and a break kitchenette, select new door/door frame, plumbing work and interior finishes in compliance with Ch. 8 of the 2012 IBC. This building is fully Fire Sprinklered. Any alterations or modifications to the buildings Fire Sprinkler or Fire Alarm system WILL REQUIRE A SEPARATE PERMIT and shall be installed per NFPA 13 & NFPA 72 as regulated by the Boise Fire Department. **JG**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIRE-Final Inspection10/25/201710/25/201710/25/2017APASS
DetailsTroy Cobbley
life safety passed
BLD-Final10/25/201710/25/201710/25/2017APASS
DetailsBob Archibald
Inspection requested by legal tenant. Life safety provisions completed. Ok for occupancy.
BLD-Final10/23/201710/25/201710/24/2017PCANC
DetailsMike Jordan
Nikki Phone #: ###-####-cancelled-GC did not call in inspection-no one can do work but him (Victor Clark)
FIRE-Final Inspection10/23/201710/25/201710/24/2017ACANC
DetailsTroy Cobbley
Nikki Phone #: ###-####-GC did not call in inspection-no one can do work but him (Victor Clark)
BLD-Conference10/23/201710/23/201710/23/2017PDONE
DetailsMike Jordan
Noted that barber college was operating with no cert. of occupancy. Fire/life/safety inspection failed, per fire corrections additional horn strobes need to be added and a fire sprinkler head is over spaced. No temp. occupancy has been given by fire inspector. It appears that a fire alarm permit has been issued and treasure valley fire is doing the sprinkler work per the tenant. A correction notice was issued stating that no occupancy is allowed until all fire issues have been resolved and building final has been scheduled and inspected. Did note that the tenant did have a sign at main entry stating that the college was closed until this wednesday.
FIRE-Final Inspection10/13/201710/13/201710/13/2017PFAIL
DetailsTroy Cobbley
Provide modifications to the fire alarm system to provide coverage to the common use areas and sprinkler system to provide coverage in the Ordinary Harard areas, need to test emergency lighting and exit signs and I need verification of the annual inspection for the fire sprinkler system

Victor Phone #: ###-####
BLD-Final10/12/201710/13/201710/13/2017AFAIL
DetailsMike Jordan
Phone #: ###-#### Inspection requested via web by Andrew Clark. No framin nspections were done. Neds fire/life/safety final.